94
UMG 511
Function
Symbol
Accuracy class
Measurem. range
Display range
Power factor
PFA, PFV
2 (IEC61557-12)
0.00 .. 1.00
0 .. 1
Short-time flicker, long-time fl.
Pst, Plt
-
-
-
Voltage drops
Udip
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage rises
Uswl
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Transient overvoltages
Utr
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage interruptions
Uint
Du - 1 cycle
-
-
Voltage inbalance
1)
Unba
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage inbalance
2)
Unb
0.5 (IEC61557-12)
10 .. 600 V
rms
0 V .. 9999 kV
Voltage harmonics
Uh
Cl. 2 (IEC61000-4-7)
to 2,5 kHz
0 V .. 9999 kV
THD of voltage
3)
THDu
2.0 (IEC61557-12)
to 2,5 kHz
0 % .. 999 %
Explanations
1) Reference to amplitude.
2) Reference to phase and amplitude.
3) Reference to basic oscillation
4) Reference to effective value.
5) Accuracy class 0.2 with ../5A converter.
Accuracy class 0.5 with ../1A converter.
* The display returns to 0 W once the max.
total working value range has been reached.
6) Calculation from fundamental harmonic oscillation.
7) Accuracy class 0.5S according IEC62053-22