57
UMG 511
Mode (delta)
If the difference of two neighbouring scanning
points exceeds the set limit value, a transient is
recognized.
• Off
- Transient monitoring is switched off.
• Automatic
- Factoring pre-setting. The limit
value is calculated automatically and is 0.2175
times the current 200ms effective value.
• Manual
- Transient monitoring uses the adjus-
table limit value under „Trns U“.
Mode (envelop)
If a scanning value exceeds the range of the enve-
lope, a transient is recognized.
• Off
- Transient monitoring is switched off.
• Automatic
- Factoring pre-setting. The enve-
lope is calculated automatically and is ± 5% of
nominal voltage.
• Manual
- Transient monitoring uses the adjus-
table envelop.
Apply AUX / MAIN
The transient monitoring is set for the main and
auxiliary measurement. You can apply the settings
from the auxiliary or main measurement.
• No
- The main and auxiliary measurement
settings are not transferred.
• Yes
- The settings of the auxiliary or main
measurement will be taken.
Содержание UMG 511
Страница 73: ...73 UMG 511 ...
Страница 98: ...98 UMG 511 Dimensional drawings Cut out size 138 0 8 x 138 0 8 mm Back Patch cable ...
Страница 99: ...99 UMG 511 Side view View from below ...