60
UMG 511
Voltage mode
Depending on the application, the voltage bet-
ween the external cables (L) or the voltage bet-
ween the external cables (L) and neutral wire (N) is
relevant for analysis of the network quality.
The setting „L-N“ is recommended for measure-
ment of the network quality in low voltage net-
works.
You should select the setting „L-L“ in medium vol-
tage networks.
C
Flicker values can only be deter-
mined if the relevant voltage L-N is
given.