background image

Prophi

®

 12R / 12 RS

20

- 19 -

Section 9     Control principle

The control response of the device can be selected in programming mode.

The controller has four different control modes:

1. Sequential connection

In sequential connection, the required capacitor stages are successively connected 

and disconnected in stages (last in - first out). The ranking of each step always 

corresponds to the power of the smallest stage.

Advantage

: Exact definition of the next capacitor to be connected in each case

Disadvantage

: Long settling time, high switching frequency of the small stages

In order to shorten the settling time, the controller switches several stages 

simultaneously  for  a  large  power-factor  requirement.  This  applies  to  all 

control types. The maximum dimensions of the simultaneously switching 

branches can be changed in expert mode.  If the value of the smallest stage 

is pre-selected, the conventional sequential connection is obtained.

2. Loop connection

In  this  variant,  the  controller  operates  in  loop  mode  (first  in  -  first  out)  which 

minimizes  the  wear  on  the  capacitor  bank,  i.e.  where  stages  are  of  equivalent 

dimensions,  the  stage  which  was  disconnected  for  the  longest  period  of  time  is 

always connected next.

Advantage

:  Balanced  utilization  of  equivalent  stages  and  thus  an  increased 

operating life of the capacitor bank.

Disadvantage

: This mode can only be used in control series with groups of the same 

stage power and long settling time, as every switching step corresponds to the value 

of the smallest stage.

3. Intelligent loop connection (default setting )

The intelligent control principle combines the advantages of the network-sparing 

loop connection (first in - first out) with a much faster settling time, even for large 

load skips, and reaches this goal with the fewest possible switching operations of the 

capacitor  stages.  The  optimized  time  response  is  achieved  by  the  simultaneous 

switching of several or larger capacitor groups as a function of the missing power 

factor  in  the  power  line.  Both  the  number  of  real  switching  frequencies  of  the 

capacitors as well as the turn-on times of the branches are considered.  

Advantage

: Reaches the target cos phi in a fast-optimized settling time with a low 

switching frequency of the capacitors.

4. Combined de-tuning (special case for combined de-tuned banks)

Within a combined de-tuned application, 2 adjoining equal steps are switched with 

just one joint choke. This pairwise de-tuning requires an appropriate closed control 

series (i.e. 1:1:1:1..., 1:1:2:2..., 1:1:2:2:4:4... or similar)

The condition for the switching behavior is defined in such a way that the number of 

activated odd steps is always greater than or equal to the number of activated even 

steps. The controller complies with the requirements of the control regime while 

largely conforming to the intelligent switching behavior.

The  particular  capacitor  steps  are  permanently  monitored. 

In  case  of  a  defect 

capacitor  or  higher  deviation  from  the  nominal  output  the  capacitor  will  be 

displayed inverted.

Содержание Prophi 12R

Страница 1: ...lefonischer Support 49 6441 9642 22 E Mail info janitza com www janitza com www janitza de Power Factor Controller Prophi 12R 12RS Manual Manual Version 4 0 E SupplyVoltage 110 440V Version 4 0 E 11 2...

Страница 2: ...ler matches capacitor discharge time UNDERCOMPENSATED Q Diff 82kvar 1 2 3 4 5 6 7 8 9 HARMONICS V 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 2 0 1 0 0 AUTO MODE ERROR MESSAGE DISPLAY MODE BARGRAPH MODE 1...

Страница 3: ...ng of fixed stages 14 Section 7 Service menu Test run 15 Section 8 Expert mode 16 8 1 Expert mode 1 8 2 Expert mode 2 18 Section 9 Control principle 19 Section 10 Display editor 20 Section 11 Initial...

Страница 4: ...vidual control series R Operation and display completely menu driven R Illuminated graphic display 128 x 64 dots R 4 quadrant operation R Automatic initialization possible R Display of several grid pa...

Страница 5: ...isplay Editor ENTER OK Confirmation storage of values Increase selected parameter HELP opens Help pages Reduce selected parameter Escape previous page value in the display Front view Rear view H HE EL...

Страница 6: ...osition The measuring current circuit must be wired with copper leads of 2 5mm The connection should be set up as shown below The specified safety regulations must be observed The measuring voltage ma...

Страница 7: ...correction between voltage and current in the meas system is done in expert mode 1 Example Meas current L1 Meas voltage L3 L2 Phase U I 90 6 L1 R L2 S L3 T N Meas current supply voltage Vb meas voltag...

Страница 8: ...rsion RS features an additional message relay The functions may be programmed as follows Alarm relay Setting under Message relay Setting under Remark Programming 14 Alarm relay INTERFACE 1 MESSAGE REL...

Страница 9: ...ER 7 FREQUENCY in Hz min max ENTER 8 TEMPERATURE in C F ENTER 9 HARMONICS V I Selection via arrow keys ENTER 10 HARMONICS THD V THD I 11 Compensation power in kvar ENTER 12 ENERGY kWh kvarh consumptio...

Страница 10: ...cessary parameters are collected evaluated and stored Under certain circumstances 3 additional test runs may be required for a proper initialization After successful finalization of AUTO INIT the devi...

Страница 11: ...tionally not be present Annex 3 the user may define a special one control series E More on this point in the control series editor in Annex 3 5 CONTROL PRINCIPLE The control preference may be selected...

Страница 12: ...ormed via the keys Continue with ENTER 11 DISCONNECTING TIME This refers to the time between disconnecting the capacitors to reduce the momentary network capacitance Setting range 1 sec 137 min long t...

Страница 13: ...2 ERROR Contact closed in case of error except voltage sag 3 ERROR inverse Contact open in case of error factory setting ERROR resp ERROR inverse is a collective report and includes the following err...

Страница 14: ...ing times By applying a control voltage 110 230V at the external input the 2nd parameter set is activated with following indicated values 19 CT primary 20 CT sec 21 End stopp 22 Control series 23 Cont...

Страница 15: ...acitor symbol AUTO Automatic normal operation The relevant output is marked by a capacitor symbol OFF The output is continuously disconnected e g for temporarily disconnecting a defective capacitor Th...

Страница 16: ...00 month after this time a service message will appear ENTER 15 27 input of a tel no for service message max 13 digits ENTER Back to 1 TEST RUN This menu point allows the user to check the settings of...

Страница 17: ...ged for special applications 6 SWITCHING POWER max 100 kvar multiples of the smallest stage This factor specifies the maximum power which may be switched in one switching step It can be used to contro...

Страница 18: ...the controller is based on a single phase measurement 3 phase CAP factory setting The measurement is converted and all outputs are displayed 3 phase presuming symmetry in the grid 1 phase CAP Display...

Страница 19: ...witch OFF the stages step by step If the measure voltage returns to the permissible range the stages will switch ON again 6 FREQUENCY 42 80 Hz 50Hz 60Hz 42 170Hz 16 7Hz Measurement by the controller i...

Страница 20: ...ge power and long settling time as every switching step corresponds to the value of the smallest stage 3 Intelligent loop connection default setting The intelligent control principle combines the adva...

Страница 21: ...ive power Note Even in Display Mode the device will continue to operate as P F controller in the background with all functions programmed Section 11 Initial operation The controller must have been ins...

Страница 22: ...ive output is switched on independent from target cos phi and controlling value in offset power programmable 4 Coupling operation parallel Coupling operation of two systems the input receives a signal...

Страница 23: ...nus CSV An optional hardware adapter IF8000 extend the device with a 2nd interface COM2 18 PROTOCOL COM2 OFF MODBUS KTR Modbus monitoring MODBUS RTU Modbus standard protocol SYNC MODE compare separate...

Страница 24: ...rminals of the measuring voltage and current l and k Check phase position See above Current in measuring range Line interruption Wrong current converter factor Current transformer short circuited Chec...

Страница 25: ...W Programmable Illuminated graphic display 128x64dot 20 1 Sequential connection loop connection or self optimized switching response Four quadrant operation YES 110 440 VAC 10 50 60Hz 30 440V L N resp...

Страница 26: ...ing up to a rating of 30 The control series editor allows the user to simply define his her own control series if the required control series is not available for any reason The last control series Co...

Страница 27: ...t Attempts Power 1 stage Control Display power factor Protocol Baudrate Adress Device type Number of BR7000 I ASCII interval Default setting ENGLISH 1000 A 5 A 12 1 INTELLIGENT 25 00 kvar 0 98 IND 230...

Страница 28: ...tems 1 Coupling is open Both systems work completely independent 2 Coupling is closed Due to controller coupling the two PFC systems are operated in PARALLEL symmetrically or in SERIES as extension Un...

Страница 29: ...ystem implements economically the advantages of a dynamic fast network Fast changing loads are compensated dynamically and basic loads slowly changing loads are compensated conventionally For designin...

Страница 30: ...ted current of the switched capacitor s In between the switching operations the current of the complete system is monitored In case the current of a step is too high default 50 this step is switched o...

Страница 31: ...coupling or extension of systems several controllers according to the applications shown in applications page 27 28 the respective message is displayed Master Slave as soon as the connection has succe...

Страница 32: ...kWh 13 DATE TIME 1 06 11 2015 10 13 40 18 CONTRAST 4 14 SOFTWARE VERSION 17 HARMONICS 3 5 7 19 16 HARMONICS THD I 16 HARMONICS THD V 7 BASIC SETTINGS RESET NO Changing of values by buttons After 60 se...

Страница 33: ...OFF C11 AUTO FIXED OFF C12 AUTO FIXED OFF 8 SWITCHING OPER C 1 123 11 ERROR MEMORY RESET NO 14 SERVICE INTERVAL 13 C POWER C 1 23 kvar MEAS C 1 25 kvar NOM 9 OPERATION TIME C 1 12h 6 SWITCH POWER max...

Страница 34: ...ERCOMPENSATED Qdiff 6 FREQUENCY 42 80 Hz 8 UNDERCOMPENSATED Qdiff 3 DELAY TIME ALARM 10 min 4 UNDERVOLTAGE 50 9 SWITCH OPERAT C1 RESET NO 9 RESET NO SWITCH OPERAT C12 10 OPERAT TIME C1 RESET NO 10 OPE...

Страница 35: ...Prophi 12R 12 RS 35 Thyristor switches different types 10 200kvar 400 690V...

Страница 36: ...Janitza electronics GmbH Vor dem Polst ck 6 D 35633 Lahnau Tel 49 6441 9642 0 E Mail info janitza de info janitza de www janitza de...

Отзывы: