8   MEASURING VOLTAGE

[ 30 ... 760]V~

Programming the measuring voltage of the system.

The values programmed here always refer to the voltage at the clamps of the 

device ! 

The voltage is selected via the 

é

 /

ê

 keys.  Save and continue with ENTER.

9   V - CONVERTER RATIO

[ NO / 230V ... 380kV ]

When  a  measuring-voltage  converter  (e.g.  for  HV-measurement)  is  used,  its 

conversion ratio should be programmed here.

(Input of prim.voltage is here, sec. voltage is automatically from item 8)

Selection via the 

é

 /

ê

 keys. Save and continue with ENTER.

10  CONNECTING TIME  

This  refers  to  the  time  between  connecting  the  capacitors  to  increase  the 

momentary network capacitance. It should be noted that in practical operation the 

real connection time is affected by the discharge time (locking time).

Setting range:

1 sec. ... 137 min. (long time for HV- networks)

Default setting: 

40 sec.

Selection is performed via the 

é

 /

ê

 keys. Continue with ENTER

11  DISCONNECTING TIME

This  refers  to  the  time  between  disconnecting  the  capacitors  to  reduce  the 

momentary network capacitance.

Setting range:

1 sec. ... 137 min. (long time for HV- networks)

Default setting: 

40 sec.

Selection is performed via the 

é

 /

ê

 keys. Continue with ENTER

12  DISCHARGE TIME

This is the time for which an individual output is blocked between connecting and 

disconnecting. This blocking time has priority over connecting and disconnecting 

times. It depends on the capacitor discharge rating and thus is specified by the 

compensation network. The discharge time of a conventional network without 

additional fast-discharge resistors or chokes should be set to no less than 40 

seconds. For setting of a second discharge time compare 'Expert Mode1' point 12

Setting range:

1 sec ...137 min.   Default setting: 60 sec.

Selection is performed via the 

é

 /

ê

 keys. Continue with ENTER

L1 (R)

L1 (R)

L2 (S)

L2 (S)

L3 (T)

L3 (T)
N

Meas. Current

Im (X/1A)                                             

Operating

  voltage

      Ub

    Meas.

  Voltage

      Um

T 2

A

T 2

A

PE

Ub

  Um

Im

High voltage                                                      Low voltage

20 kV / 400 V

20000

100

Содержание Prophi 12R

Страница 1: ...lefonischer Support 49 6441 9642 22 E Mail info janitza com www janitza com www janitza de Power Factor Controller Prophi 12R 12RS Manual Manual Version 4 0 E SupplyVoltage 110 440V Version 4 0 E 11 2...

Страница 2: ...ler matches capacitor discharge time UNDERCOMPENSATED Q Diff 82kvar 1 2 3 4 5 6 7 8 9 HARMONICS V 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 2 0 1 0 0 AUTO MODE ERROR MESSAGE DISPLAY MODE BARGRAPH MODE 1...

Страница 3: ...ng of fixed stages 14 Section 7 Service menu Test run 15 Section 8 Expert mode 16 8 1 Expert mode 1 8 2 Expert mode 2 18 Section 9 Control principle 19 Section 10 Display editor 20 Section 11 Initial...

Страница 4: ...vidual control series R Operation and display completely menu driven R Illuminated graphic display 128 x 64 dots R 4 quadrant operation R Automatic initialization possible R Display of several grid pa...

Страница 5: ...isplay Editor ENTER OK Confirmation storage of values Increase selected parameter HELP opens Help pages Reduce selected parameter Escape previous page value in the display Front view Rear view H HE EL...

Страница 6: ...osition The measuring current circuit must be wired with copper leads of 2 5mm The connection should be set up as shown below The specified safety regulations must be observed The measuring voltage ma...

Страница 7: ...correction between voltage and current in the meas system is done in expert mode 1 Example Meas current L1 Meas voltage L3 L2 Phase U I 90 6 L1 R L2 S L3 T N Meas current supply voltage Vb meas voltag...

Страница 8: ...rsion RS features an additional message relay The functions may be programmed as follows Alarm relay Setting under Message relay Setting under Remark Programming 14 Alarm relay INTERFACE 1 MESSAGE REL...

Страница 9: ...ER 7 FREQUENCY in Hz min max ENTER 8 TEMPERATURE in C F ENTER 9 HARMONICS V I Selection via arrow keys ENTER 10 HARMONICS THD V THD I 11 Compensation power in kvar ENTER 12 ENERGY kWh kvarh consumptio...

Страница 10: ...cessary parameters are collected evaluated and stored Under certain circumstances 3 additional test runs may be required for a proper initialization After successful finalization of AUTO INIT the devi...

Страница 11: ...tionally not be present Annex 3 the user may define a special one control series E More on this point in the control series editor in Annex 3 5 CONTROL PRINCIPLE The control preference may be selected...

Страница 12: ...ormed via the keys Continue with ENTER 11 DISCONNECTING TIME This refers to the time between disconnecting the capacitors to reduce the momentary network capacitance Setting range 1 sec 137 min long t...

Страница 13: ...2 ERROR Contact closed in case of error except voltage sag 3 ERROR inverse Contact open in case of error factory setting ERROR resp ERROR inverse is a collective report and includes the following err...

Страница 14: ...ing times By applying a control voltage 110 230V at the external input the 2nd parameter set is activated with following indicated values 19 CT primary 20 CT sec 21 End stopp 22 Control series 23 Cont...

Страница 15: ...acitor symbol AUTO Automatic normal operation The relevant output is marked by a capacitor symbol OFF The output is continuously disconnected e g for temporarily disconnecting a defective capacitor Th...

Страница 16: ...00 month after this time a service message will appear ENTER 15 27 input of a tel no for service message max 13 digits ENTER Back to 1 TEST RUN This menu point allows the user to check the settings of...

Страница 17: ...ged for special applications 6 SWITCHING POWER max 100 kvar multiples of the smallest stage This factor specifies the maximum power which may be switched in one switching step It can be used to contro...

Страница 18: ...the controller is based on a single phase measurement 3 phase CAP factory setting The measurement is converted and all outputs are displayed 3 phase presuming symmetry in the grid 1 phase CAP Display...

Страница 19: ...witch OFF the stages step by step If the measure voltage returns to the permissible range the stages will switch ON again 6 FREQUENCY 42 80 Hz 50Hz 60Hz 42 170Hz 16 7Hz Measurement by the controller i...

Страница 20: ...ge power and long settling time as every switching step corresponds to the value of the smallest stage 3 Intelligent loop connection default setting The intelligent control principle combines the adva...

Страница 21: ...ive power Note Even in Display Mode the device will continue to operate as P F controller in the background with all functions programmed Section 11 Initial operation The controller must have been ins...

Страница 22: ...ive output is switched on independent from target cos phi and controlling value in offset power programmable 4 Coupling operation parallel Coupling operation of two systems the input receives a signal...

Страница 23: ...nus CSV An optional hardware adapter IF8000 extend the device with a 2nd interface COM2 18 PROTOCOL COM2 OFF MODBUS KTR Modbus monitoring MODBUS RTU Modbus standard protocol SYNC MODE compare separate...

Страница 24: ...rminals of the measuring voltage and current l and k Check phase position See above Current in measuring range Line interruption Wrong current converter factor Current transformer short circuited Chec...

Страница 25: ...W Programmable Illuminated graphic display 128x64dot 20 1 Sequential connection loop connection or self optimized switching response Four quadrant operation YES 110 440 VAC 10 50 60Hz 30 440V L N resp...

Страница 26: ...ing up to a rating of 30 The control series editor allows the user to simply define his her own control series if the required control series is not available for any reason The last control series Co...

Страница 27: ...t Attempts Power 1 stage Control Display power factor Protocol Baudrate Adress Device type Number of BR7000 I ASCII interval Default setting ENGLISH 1000 A 5 A 12 1 INTELLIGENT 25 00 kvar 0 98 IND 230...

Страница 28: ...tems 1 Coupling is open Both systems work completely independent 2 Coupling is closed Due to controller coupling the two PFC systems are operated in PARALLEL symmetrically or in SERIES as extension Un...

Страница 29: ...ystem implements economically the advantages of a dynamic fast network Fast changing loads are compensated dynamically and basic loads slowly changing loads are compensated conventionally For designin...

Страница 30: ...ted current of the switched capacitor s In between the switching operations the current of the complete system is monitored In case the current of a step is too high default 50 this step is switched o...

Страница 31: ...coupling or extension of systems several controllers according to the applications shown in applications page 27 28 the respective message is displayed Master Slave as soon as the connection has succe...

Страница 32: ...kWh 13 DATE TIME 1 06 11 2015 10 13 40 18 CONTRAST 4 14 SOFTWARE VERSION 17 HARMONICS 3 5 7 19 16 HARMONICS THD I 16 HARMONICS THD V 7 BASIC SETTINGS RESET NO Changing of values by buttons After 60 se...

Страница 33: ...OFF C11 AUTO FIXED OFF C12 AUTO FIXED OFF 8 SWITCHING OPER C 1 123 11 ERROR MEMORY RESET NO 14 SERVICE INTERVAL 13 C POWER C 1 23 kvar MEAS C 1 25 kvar NOM 9 OPERATION TIME C 1 12h 6 SWITCH POWER max...

Страница 34: ...ERCOMPENSATED Qdiff 6 FREQUENCY 42 80 Hz 8 UNDERCOMPENSATED Qdiff 3 DELAY TIME ALARM 10 min 4 UNDERVOLTAGE 50 9 SWITCH OPERAT C1 RESET NO 9 RESET NO SWITCH OPERAT C12 10 OPERAT TIME C1 RESET NO 10 OPE...

Страница 35: ...Prophi 12R 12 RS 35 Thyristor switches different types 10 200kvar 400 690V...

Страница 36: ...Janitza electronics GmbH Vor dem Polst ck 6 D 35633 Lahnau Tel 49 6441 9642 0 E Mail info janitza de info janitza de www janitza de...

Отзывы: