background image

www.janitza.com

JPC70

9

4. 2 

Performance features

General information

•  Integrated front panel unit with the dimensions 197 x 140 mm
•  Connection via Ethernet to the Janitza gateway devices: UMG 

512/509/605/604/96RM-E and ProData

•  Representation of up to 10 Janitza UMG 20CM devices
•  TFT display 800 x 480 pixels
•  Operation via touch screen
•  2 x USB 2.0 type A interfaces
•  Ethernet interface
•  Operating temperature range -20 °C – +60 °C

Visualization

•  Representation of all current and energy values
•  Display of the last maximum value of the connected devices
•  Topology view of the bus system
•  Visualization of the main and auxiliary measurement
•  Monitoring of up to 200 current channels

Configuration

•  Dynamic topology configuration with freely selectable number of devices
•  Group transfer of configuration of up to several devices
•  Import and export of device configurations via USB
•  Labeling of individual current circuits
•  Threshold value can be set per channel

Содержание JPC70

Страница 1: ...8 Smart Energy Panel JPC70 User Manual and Technical Data Janitza electronics GmbH Vor dem Polst ck 6 35633 Lahnau Germany Support tel 49 6441 9642 22 Fax 49 6441 9642 30 Email info janitza com www ja...

Страница 2: ...ription 8 4 1 Operating concept 8 4 2 Performance features 9 4 3 Product overview 10 5 Assembly 12 5 1 Installation location 12 5 2 Installation position 12 5 3 Fastening 12 5 4 Ground 13 6 Installati...

Страница 3: ...User management 25 7 6 1 User settings 25 7 7 System 27 7 7 1 Device settings 27 7 7 2 Modbus TCP 27 7 7 4 Time setting 28 7 7 5 Display 28 7 7 3 TCP IP settings 28 7 8 Email configuration 29 8 Servi...

Страница 4: ...belong to the respective holders of these rights 1 3 Technical changes Make sure that the installation instructions match your device First make sure you have read and understood the document accompa...

Страница 5: ...l must be read the manual before using the device must be kept and remain available for reference during the entire service life of the product Also observe the applicable legal and safety requirement...

Страница 6: ...ltages present in the device even after it is disconnected from the supply voltage Fit wire end ferrules on the conductors made of individual wires Only connect screw type terminals with matching numb...

Страница 7: ...when for example the device has visible damage no longer functions despite an intact power supply was subjected to extended periods of unfavorable conditions e g storage outside of the permissible cl...

Страница 8: ...vices installation in permanently installed switch cabinets or small installation distributors 4 1 Operating concept You can program the device in several different ways and or display measured values...

Страница 9: ...t interface Operating temperature range 20 C 60 C Visualization Representation of all current and energy values Display of the last maximum value of the connected devices Topology view of the bus syst...

Страница 10: ...capable a mean value is generated when the screen is touched in multiple places simultaneously This averaged position value is evaluated by the application Therefore since the entire touch area is lar...

Страница 11: ...ctor The connection to the ground potential must be made as short as possible and adequately strong 4 mm via the provided flat plug connection Faston 6 3 mm 2 Unshielded conductors All unshielded cond...

Страница 12: ...free surface Unevenness can cause damage to the display and result in the penetration of dust and water Fig 4 Rear view with retaining clamps 1 Insert the front side of the device in the provided ins...

Страница 13: ...g The cable shield e g Ethernet is discharged via the ground plate Ground connection WARNING The ground potential ground lug on the device and the GND connection of the voltage supply are connected in...

Страница 14: ...via the plug type terminals on the rear side of the device Before connecting the supply voltage ensure that the supply voltage matches the specifications form the technical data See section 9 on Page...

Страница 15: ...egments Slave Fig 10 Bus structure representation Slave Slave Slave Repeater Slave Slave Slave Master Speisung notwendig power supply necessary Busabschluss eingeschaltet bus terminator on T T T T T D...

Страница 16: ...rent voltage values of the integrated slave devices is shown on the start screen By touching the values in the overview of a slave device you open its other values the configuration menu and the alarm...

Страница 17: ...igning a permanent IP address can cause problems in networks See 7 7 3 on Page 28 7 2 1 Integrating the master device Proceed as follows to connect the device to a master 1 Log in as an administrator...

Страница 18: ...determine the Modbus address 8 Configure the addresses of all connected slave devices in this manner 9 Save the settings by pressing the Save button 10 Touch the version number date or time in the st...

Страница 19: ...is purpose open the configuration menu of a slave device as described in 7 2 2 Fig 15 Measured values overview You switch between the available measuring channels of the device with the arrow buttons...

Страница 20: ...gured with the JPC70 With the Set IO selection box you can define whether outputs should be activated when the warning level or alarm level is exceeded Low pass filter You can activate the low pass fi...

Страница 21: ...devices connected in the bus Fig 18 Configuration interface of the slave devices in the JPC70 Here you have the option to adopt energy meters and minimum maximum current values for all slave devices...

Страница 22: ...more information refer to the user manual of the slave device In the process the threshold values for triggering a warning and threshold values for trigging an alarm are defined If the respective thre...

Страница 23: ...e to activate deactivate the alarm system It is possible to receive messages via email in addition to the messages on the JPC70 See 7 8 Email configuration on Page 29 7 4 Master devices Call up additi...

Страница 24: ...bar Messages can be acknowledged individually with the Acknowledge selected alarm button or all at once by pressing the Acknowledge all alarms button 7 5 1 Alarm history You open the alarm history by...

Страница 25: ...gs can be acknowledged Operator Standard role for logged in users They can also acknowledge and configure alarms and warnings in addition to the ViewOnly user Administrator Device settings can be carr...

Страница 26: ...the User name input field 5 Enter the user s fill name in the Full name input field optional 6 Select the desired role in the Group role selection list 7 Select the system language for the new user i...

Страница 27: ...ings of a device and importing them to another device For this purpose proceed as follows 1 Connect the JPC70 via one of the USB interfaces to a FAT32 formatted USB data carrier The check mark next to...

Страница 28: ...ton next to the IP address input field 4 Press the Save button to save the configuration 7 7 4 Time setting The time for the JPC70 can be entered manually with the Clock menu item or obtained via an N...

Страница 29: ...ail proceed as follows 1 Enter the host address of the email server in the Host IP input field 2 Enter the valid login data for the email server in the User name and Password input fields Learn about...

Страница 30: ...ulations e g as Electronic waste Plastic Metal or commission a certified disposal company with the scrapping 8 4 Service In case of any questions which are not described in this manual please contact...

Страница 31: ...100BASE TX Display Type Color TFT Diagonal 7 Colors 16 7 million RGB 8 bits per channel Resolution WVGA 800 x 480 pixels Contrast typically 600 1 Touchscreen Yes Electrical properties Supply voltage...

Страница 32: ...170 73 26 27 27 8 184 8 112 9 42 8 170 73 26 27 27 8 184 8 112 9 150 5 140 197 5 25 5x 12 5 13 8 1 127 9 42 8 R2 Fig 28 View from above Fig 29 Front view Fig 30 Rear view 170 73 26 27 27 8 184 8 112...

Отзывы: