Appendix 3 – Selection of cables and accessories
Nominal current
25 A
35 A
50 A
60 A
75 A
100 A
150 A
Phase cross section, mm²
16 mm²
16 mm²
25 mm²
25 mm²
35 mm²
35 mm²
50 mm²
Phase line N, mm²
25 mm²
25 mm²
35 mm²
35 mm²
35 mm²
50 mm²
70 mm²
PE cable, mm²
16 mm²
16 mm²
16 mm²
16 mm²
16 mm²
16 mm²
16 mm²
Power terminal screws
M6
M6
M8
M8
M8
M8
M8
PE terminal screw
M6
M6
M6
M6
M6
M6
M6
Circuit breaker rated
current
63 A
63 A
100 A
100 A
100 A
160 A
200 A
CT line
Less than 15 m: RVVSP 2×2.5 mm²; 15 m - 30 m: RVVSP 2×4 mm²;
Over 30 m: Contact Janitza
CT ratio range
150:5 to 10,000:5
Note
If there are certain requirements concerning the cable temperature,
the specification of the cable must be enhanced
Note:
1. If the current of the fundamental is the main part of the total current (fundamental and
harmonic), the wire cross section of the N-conductor should be 3 times larger than the
phase conductor cross section.
2. The CT ratio should be selected to be 1.5 to 4 times that of the maximum
load current.
3. The rated current of the circuit breaker should be selected to be 1.2 times
the rated capacity of the AHF, or more.