35
www.janitza.de
800-DI14 module
11. Technical data
General
Net weight (with plug-in terminals)
73 g (0.16 lb)
Device dimensions (without plug-in terminals)
W = 18 mm (w = 0.71 in), H = 90 mm (h = 3.54 in),
D = 76 mm (d = 2.99 in)
Mounting orientation
As desired
Fastening/mounting -
Suitable DIN rails - (35 mm / 1.38 in)
TS 35/7.5 according to EN 60715
TS 35/10
TS 35/15 x 1.5
Protection against foreign matter and water
IP20 according to EN60529
Impact resistance
IK07 according to IEC 62262
Environmental conditions during operation
The module
· Is to be operated with a UMG 801 basic device with firmware as of 1.5.0.
· Is for weather-protected and stationary use.
· Fulfills operating conditions according to DIN IEC 60721-3-3.
· Has protection class II according to IEC 60536 (VDE 0106, part 1), a ground wire connection is not required!
Working temperature
-10 °C (14 °F) .. +55 °C (131 °F)
Relative humidity
5 to 95% at 25 °C (77 °F), no condensation
Pollution degree
2
Ventilation
No forced ventilation required.
Transport and storage
The following specifications apply for devices transported and stored in the original packaging.
Free fall
1 m (39.37 in)
Temperature
K55 - -25 °C (-13 °F) to +70 °C (158 °F)
Relative humidity
0 to 95% at 25 °C (77 °F), no condensation
Digital inputs
14 digital inputs, solid state relays, not short-circuit proof.
Maximum counter frequency
20 Hz
Input signal applied
18 .. 28 V DC (typically 4 mA)
Input signal not applied
0 .. 5 V DC, current less than 0.5 mA
Interface and energy supply
JanBus (proprietary)
Via bus connector
Max. bus length (JanBus) 100 m.
Supply voltage (via JanBus interface)
24 V
Содержание 800-DI14
Страница 7: ...7 www janitza de 800 DI14 module...
Страница 17: ...17 www janitza de 800 DI14 module...
Страница 21: ...21 www janitza de 800 DI14 module...
Страница 39: ...39 www janitza de 800 DI14 module...
Страница 42: ...42 800 DI14 module www janitza de...
Страница 43: ...43 www janitza de 800 DI14 module...