www.janitza.com
UMG 804
25
8.2.1
Current Transformer Types
1
2
3
1. Plug the branch CTs into the polarized
connectors on the Interface Board,
refer to
2. Place the CT on the correct conduc-
tor being sure to align the CT with the
correct terminal and breaker conductor
skipping empty conductors,
refer to
3. Snap the CT closed around the con-
ductor and make sure latch is locked,
refer to
INFORMATION
The CT Orientation is not important; the
system will auto correct,
1
2
3