LD/LJ Side Wall Vent Kit Instructions

Page 1

 

Installation Kit Instructions 

  

Installation Instructions For 

LD/LJ Side Wall Vent Kit

 WARNING

FOR YOUR SAFETY - 

This product must be installed and serviced by personnel qualified in pool/spa 

heater installation. Improper installation and/or operation can create carbon monoxide gas and flue gases 

which can cause serious injury, property damage, or death. For indoor installations, as an additional  

measure of safety, Zodiac Pool Systems, Inc. strongly recommends installation of suitable Carbon  

Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces. Improper  

installation and/or operation will void the warranty.

These instructions are to be used with the following Jandy

®

 Replacement Kits:

R0412001--Side Wall Vent Installation Kit, Jandy Pool Heater Model LD/LJ 125 and 175.

R0412003--Side Wall Vent Installation Kit, Jandy Pool Heater Model LD/LJ 250.

R0412005--Side Wall Vent Installation Kit, Jandy Pool Heater Model LD/LJ 325 and 400.

 WARNING

If the information in these instructions is not followed exactly, a fire or explosion may result 

causing property damage, personal injury or death.

This document gives information on installing 

the side wall venting kit for all Jandy LD and LJ model 

pool/spa heaters. This kit is used to adapt an LD or LJ 

model heater for use when horizontal side wall vent-

ing is required or desirable for installation. The wiring 

diagrams provided with the kit assure proper installa-

tion. The included Tjernlund UC1 Universal Control is 

equipped with an adjustable post purge timing which al-

lows for field settings to be compatible with the ignition 

sequence of the model LD and LJ. The control manu-

facturer's instructions are included for detailed reference 

and troubleshooting the control.

This kit supplies you with all of the major compo-

nents of the system that you will need to install the side 

wall vent. Due to the different possible configurations 

for venting, we do not supply the vent pipe, elbows, 

tees, wiring or conduit needed to connect the heater 

to the vent blower. However, the appropriate size vent 

reducer, to transition from the vent pipe to the blower, is 

included for your convenience. 

If you need help with the installation of the Side 

Wall Vent Kit or more information to clarify the follow-

ing procedure, call the Zodiac Pool Systems, Inc. Tech-

nical Support Department at (800) 822.7933 extension 

260. These instructions must be followed exactly. Read 

through the instructions completely before starting the 

procedure.

Before starting the procedure, use the parts list at 

the back of these instructions to identify the parts that 

are in your kit. If any parts are missing from the kit 

please call your local Jandy distributor for assistance. 

H0275000D

1.   Prepare The Heater

In general, locate the heater as described in the LD 

or LJ Installation and Operation Manual, provided with 

the heater. All requirements for heater installation and 

location are the same as the installation requirements 

of the manual. Only the section on venting of indoor 

installations will change.

Jandy LD and LJ heaters are shipped in the out-

door configuration with the low profile top installed. 

The heater will need to be fitted with a draft hood in 

order to properly connect the side wall vent kit. Use the 

following table to verify that the correct draft hood is 

fitted to the heater (see Table 1).

Instructions for the installation of the draft hood 

are included with the draft hood kit. Install the draft 

hood according to the manufacturer's instructions.

Table 1.  Draft Hood and Vent Pipe Diameter

HEATER 

SIZE

DRAFT 

HOOD 

DIA.

VENT 

PIPE 

DIA.

JANDY 

DRAFT 

HOOD KIT 

NUMBER

USED WITH 

SIDE WALL 

VENT KIT 

NUMBER

125

5”

5”

10561501

R0412001

175

6”

6”

10561502

R0412001

250

7”

6”

10561503

R0412003

325

8”

8”

10561504

R0412005

400

9”

9”

10561505

R0412005

Содержание R0412001

Страница 1: ...u with all of the major compo nents of the system that you will need to install the side wall vent Due to the different possible configurations for venting we do not supply the vent pipe elbows tees w...

Страница 2: ...nfiguration consists of an initial vertical section of vent pipe see Figure 2 Either configuration must meet the following constraints 1 The draft hood must be connected directly to the heater as per...

Страница 3: ...he heater with power 2 Remove the heater door 3 Locate the common terminal on the transformer There will be a yellow wire with a piggy back terminal attached to the transformer and a green wire with a...

Страница 4: ...mp relay over the bracket and use the screws removed earlier to secure the bracket and the pump relay to the back panel see Figure 6 Figure 3 Remove the Cover of the High Voltage Assembly Figure 4 Mou...

Страница 5: ...or bracket included in the kit must be installed to deflect the air around the igniter allowing it to heat enough to ignite the gas The air deflector bracket is not needed on the mod el LD heater beca...

Страница 6: ...he side of the heater using a conduit connector and nut 3 Strip the insulation from each of the wires that will lead to the UC1 controller about 1 2 from the end 4 Locate the yellow wire installed on...

Страница 7: ...LD LJ Side Wall Vent Kit Instructions Page 7 Figure 10 Wiring Diagram for Connecting a Model LD Heater to a Side Wall Power Venter F2 F1...

Страница 8: ...Page 8 Figure 11 Wiring Diagram for Connecting a Model LJ Heater to a Side Wall Power Venter...

Страница 9: ...ler NOTE Power connection to the controller requires a three 3 conductor copper wire harness that is run in a conduit from the power supply to the con troller These components must be supplied by the...

Страница 10: ...tch es must remain in the off down position see Figure 12 3 5 2 Jumper Placement in the UC1 Controller Installed on a Model LD Heater The Jandy LD heater uses a 24V signal to activate the power venter...

Страница 11: ...peration and enables the heater to begin its ignition se quence 3 When the igniter is hot enough the gas valve opens and burner ignition takes place 4 When the call for heat ends the burners are shut...

Страница 12: ...EDUCER 9 X 6 FOR MODEL 400 1 11 WIRE NUTS 3 3 3 12 YELLOW WIRE ASSEMBLY MODEL LD ONLY 1 1 1 13 PURPLE WIRE ASSEMBLY 1 1 1 14 1 4 DOUBLE MALE X 1 4 FEMALE CONNECTOR MODEL LD ONLY 1 1 1 15 BLOWER RELAY...

Отзывы: