background image

Model LG Pool and Spa Heater

Page 31

If no voltage is detected at test point 3, the wire

between the gas valve and the fusible link is broken.
Replace the wire.

If there is a minimum of 220mV at test point 3,

move the black meter lead to the other terminal of the
fusible link (test point 4).

If no voltage is detected at test point 4, the

fusible link has failed. This indicates higher than
normal temperatures in the component compartment
(vestibule). Normal component compartment tempera-
ture is well below 300

o

F. The fusible link is designed

to fail at temperatures above 305°F. Excessive tem-
perature might be due to a blocked flue or heat ex-
changer. Clean the heat exchanger and clear the flue
and vent of any restrictions. Sometimes the fusible
link fails due to flame roll-out. Flame roll-out may be
caused by delayed ignition or downdrafting in windy
areas. Thoroughly investigate the causes for flame
roll-out and correct the problem when replacing the
fusible link.

10.4.4

Fireman Switch and External
Interlocks

Check the voltage going to the external device.

Touch the black lead of the meter to the fireman
switch terminal strip where the white wire from the
fusible link is connected (test point 5). The meter
should read at least 220mV. If the voltage is less than
220mV, there may be a bad connection or wire
between the fusible link and the terminal strip. The
wire may need to be replaced. If voltage of 220mV or
more is detected at test point 5, move the black lead of
the meter to the fireman switch terminal strip connec-
tion where the white wire from the high limit is
connected (test point 6). The meter should read at least
220mV. If there is no voltage, the time clock switch or
other external interlock may be mis-adjusted, mis-
connected or defective. Correct this external problem.

10.4.5

Limit Switches

Since the limit switches are not easily accessible,

you can check the voltage going into the component
after the limit switches in the circuit. If voltage is
detected there, then the limit switches are closed and
are operational.

Check the voltage going to the water pressure

switch. Leave the red voltmeter lead in place at test
point 1. Touch the black lead of the meter to the
terminal of the water pressure switch where the white
wire is connected (test point 11).

If the voltage is less than 220mV, there may be a

bad connection, a partial short or a faulty sensor. If
there is no voltage, one of the limit switches is open.
This is normally due to excessive water temperature,
which should be thoroughly investigated before

replacement of limit switches. Excessive water
temperature may be caused by low water flow. Water
flow deficiency may be due to obvious problems such
as a defective pump or blocked water filter. Alterna-
tively, excessive water temperature may be due to
over-firing, or to a problem with the water piping or
the heater's internal bypass control. Over-firing might
be a result of an incorrect gas orifice or supply of
propane gas to a heater intended for natural gas.

If there are no such fundamental problems,

identify which of the switches is open. Limit switch
access is through the limit switch cover on the inlet/
outlet header. Remove the cover and retainer bracket
from the high limit switches and remove the limit
switches from the wells. Move the black lead of the
meter to the terminal on the 150°F limit switch (test
point 7) that is connected to the fireman switch
terminal block. Less than 220mV at this point means
that the wire between the terminal block and the limit
switch has a poor or broken connection or a partial
short. Replace the wire assembly. If at least 220mV is
detected at test point 7, then move the black lead of
the meter to the other terminal of the 150°F limit
switch (test point 8). Low or no voltage here means
that the limit is open and must be replaced.

If 220mV or more is detected at test point 8,

move the black lead of the meter to the terminal on the
135°F limit switch (test point 9) that is connected to
the 150°F limit switch. Less than 220mV at this point
means that the wire between the two limit switches has
a poor or broken connection or a partial short. Replace
the wire assembly. If at least 220mV is detected at test
point 9, then move the black lead of the meter to the
other terminal of the 135°F limit switch (test point
10). Low or no voltage here means that the limit is
open and must be replaced. If voltage is detected at
test point 10, move the black lead of the meter to the
terminal of the water pressure switch where the white
wire from the high limits is connected (test point 11).
Less than 220mV at this point indicates that the wire
connecting the high limits to the water pressure switch
is faulty or poorly connected. Correct the problem or
replace the wire.

Note:

 The limit switches have different trip

points, and it is important that replacements
are correct. The 150°F switch has a red dot on
the top of the brass fitting, and must be
installed in the lower (horizontal) well in the
header. The 135°F switch has no dot and must
be installed in the upper (vertical) well in the
header.

Содержание LG125

Страница 1: ...H0264600A InstallationandOperationData WARNING If these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasol...

Страница 2: ...Generators and Sanitizing Chemicals 16 SECTION 6 Electrical Connection 6 1 Main Power 17 6 2 Bonding 17 6 3 Auxiliary Time Clock Wiring 17 SECTION 7 Operating Instructions 7 1 Normal Operation 17 7 2...

Страница 3: ...Tubs recommended by the U S Consumer Product Safety Commission should be observed when using the spa WARNING The U S Consumer Product Safety Commission warns that elevated water temperature can be ha...

Страница 4: ...specified on the back cover of thismanual Make all warranty claims to an authorized Jandy representative or directly to the factory Claims must include the heater serial number and model this informa...

Страница 5: ...helter and Outdoor 2 MinimumClearanceFromCombustibleMaterial See Table 2 in Section 2 3 2 3 Gas Pipe Heater Gas Valve Connection Natural Gas 3 4 NPT LP Gas 3 4 NPT For diameter of gas line from meter...

Страница 6: ...l application and installationprocedurescompletelybeforecontinuing theinstallation 2 2 Field Assembly The Lite2 heater is shipped from the factory with the top assembly in the low profile configuratio...

Страница 7: ...locations where it can cause damage by water or condensate leakage If this is not possible provide a suitable drain pan to catch and divert any leakage The pan must not block natural flow of air aroun...

Страница 8: ...ation Lite2 heaters can be installed in the low profile top configuration as received from the factory or with an optional high wind vent cap Locate the heater in an open unroofed area Do not install...

Страница 9: ...0 91 m from vertical surfaces e g nearby buildings and walls The addition of a vent cap may be necessary In Florida it is required that the heater be se curely fastened to the equipment pad Use a siz...

Страница 10: ...ly through an outside wall each opening should have a minimum free area of one square inch per 4 000 BTU h 1 2kW input of the total input rating of all appliances in the enclosed area If air is provid...

Страница 11: ...be desirable to add a vent cap directly to the top of the heater In all cases vent pipes and caps must be of the same diameter as the exhaust outlet of the heater Approved vent caps may be obtained t...

Страница 12: ...st be used be sure to carefully inspect the venting system to ensure that it is in good condition and continues to be appropriate for the Lite2 heater Replace any parts that are not in good and servic...

Страница 13: ...ring the piping pressure test 7 If the gas supply pressure is less than required check for undersized pipe between the meter and the heater a restrictive fitting or an undersized gas meter Gas supply...

Страница 14: ...your manom eter The pressure will be zero when the heater is not running When the heater is operating the manifold gas pressure should be 4 0 WC for natural gas heaters and 9 0 WC for LP gas heaters...

Страница 15: ...header of the Lite2 comes equipped with an automatic flow control valve The automatic flow control valve maintains the proper flow through the heater at rates up to approximately 125 Gallons Per Minut...

Страница 16: ...retainer bracket off the bulb flange and remove the bulb from the header see Figure 10 Pull pressure switch tube through the hole in the vestibule cover and into the vestibule controls compart ment t...

Страница 17: ...tor are installed into the grooves on the front and rear combustion chamber heat shield panels Be sure the sheet metal panels are not pinching any wires 22 Attach the flue collector hold down clamps t...

Страница 18: ...m any area occupied during servicing 5 7 Auxiliary Components Chlorinators Ozone Generators and Sanitizing Chemicals The Lite2 heater is manufactured with materials that are not compatible with high c...

Страница 19: ...itch into the heater wires see Figure 16 1 Remove heater door 2 Remove the factory installed wire between terminals 1 and 2 on the terminal strip see Figure16 3 Connect the wires from the time clock a...

Страница 20: ...Page 18 Figure 17 LG Connection Schematic Wiring Diagram...

Страница 21: ...n the pool and that the surface level is above the skimmer or other inlet of the pool s filter system Confirm that pool water is flowing normally through the pool system and equipment With any new poo...

Страница 22: ...F 21 C to 40 C Use an accurate pool thermometer to determine the best water temperature for your uses The Lite2 temperature control panel has a rocker switch to turn the heater on and off It also has...

Страница 23: ...If pilot goes out repeat steps 1 through 6 TO SHUT OFF HEATER To shut off main burners turn gas control knob clockwise until it stops at PILOT For complete shut off press down slightly on knob while t...

Страница 24: ...1 Set the control panel rocker switch to the OFF position see Figure 18 2 Set the Pool temperature control to the Max position 3 Turn filter pump on If a two speed pump is used make sure it is at high...

Страница 25: ...y 13 If the temperature rise is within the correct range complete the procedure as follows a Turn heater OFF b Wait 3 minutes turn filter pump OFF c Remove thermometer and Pete s plug d Replace the dr...

Страница 26: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy Table 7 Chemical Concentration Levels Test Recommended Level Free Chlorine or 1 0 to 3...

Страница 27: ...er or page 21 of this manual 8 3 Inspection and Service The Lite2 LG heater is designed and constructed heater to provide long performance life when installed and operated properly under normal condit...

Страница 28: ...bove burner surface see Figure 22 7 Inspect the gas and electronic controls including the following a High temperature limit switch b Water pressure switch c Automatic gas valve d Fusible Link e Tempe...

Страница 29: ...equate C Replace with heater of higher input 7 Heater pounding A Inadequate water flow A Check temperature rise between inlet and outlet heater or knocking through heater piping See section 7 6 for re...

Страница 30: ...that there is no block age of the vent or louvers which supply combustion air to the burners 10 2 Natural Draft Combustion System The Lite2 model LG pool heater has an atmo spheric combustion system T...

Страница 31: ...eater If this current is broken at any time the gas valve is immedi ately shut off and the heater stops firing This voltage is also used to activate the gas valve s pilot coil which allows gas to flow...

Страница 32: ...ction 7 3 check the voltage reading between the PP terminal on the gas valve test point 1 and the TH terminal on the gas valve test point 17 If the meter shows less than 220mVDC then there is a proble...

Страница 33: ...n This is normally due to excessive water temperature which should be thoroughly investigated before replacement of limit switches Excessive water temperature may be caused by low water flow Water flo...

Страница 34: ...he internal contacts are working correctly The volt meter reading should drop to zero when the switch is OFF and return to at least 220mV when the switch is placed back in the ON position 10 4 7 2 Var...

Страница 35: ...Model LG Pool and Spa Heater Page 33 Figure 24 Test Point Identification Diagram...

Страница 36: ...000 67 Flange Sleeve 2 All S0078200 68 Flange Bolt All F0031700 69 Flange Gasket 1 1 2 2 All S0078100 70 Rubber Grommet for Drain Plug All R0316300 71 Grommet Slitted Not Shown All S0071100 72 Brass C...

Страница 37: ...125 S0000300 88 Heat Exchanger End Baffles 2 Required 125 400 R0332301 05 FIREBOX COMPONENTS 89 Complete Combustion Chamber Assy 125 400 R0316701 05 JACKET COMPONENTS 90 Door with Latch 125 400 R03436...

Страница 38: ...R TRAY SEE NEXT PAGE FOR DETAIL 44 45 46 54 48 47 49 50 53 UNITED STATES 70 70 73 73 89 90 91 92 93 94 95 96 HEAT EXCHANGER SEE NEXT PAGE FOR DETAIL TEMPERATURE CONTR0L SEE NEXT PAGE FOR DETAIL 19 34...

Страница 39: ...e 37 16 14 7 6 8 5 2 4 15 17 32 26 74 85 43 42 69 41 38 39 68 65 67 66 78 81 76 94 79 33 24 25 37 64 75 3 11 18 12 40 36 35 72 77 80 13 1 58 86 84 85 63 60 63 62 83 57 60 61 62 59 61 56 27 28 22 21 23...

Страница 40: ...se of non factory authorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing ch...

Отзывы: