b. High altitude (H) - 2,000 to 4,500 feet

(610 to 1370 m)

FOR PROPANE GAS
a. Factory Released  - 0 to 4,500 feet

(610 to 1370 m)

5.

Use only wrought steel piping or when permitted by

local codes, other rigid piping material.  Do not use

flexible gas connectors, which restrict gas flow to the

heater.

6.

Table 4 specifies sizing for gas supply piping based

on 1/2” WC (3.45 kPa) pressure drop in the piping.

Larger piping may be necessary if the local gas

supply is at pressures which will not guarantee

adequate pressure at the heater. Table 5 specifies the

maximum and minimum supply pressures necessary

at the heater 

when it is operating.

7.

Install a sediment trap (drip leg) ahead of the gas

controls (see Figure 7). Fit the trap with a  threaded

cap which can be removed for cleaning.

8.

Install a manual gas shut-off valve for service and

safety. Do not use a restrictive gas cock.

CAUTION

Permanent damage to the gas valve will occur

if the following procedures are not followed.

9.

Disconnect the heater and its individual shutoff valve

from the gas supply system during pressure testing of

the system at pressures higher than 1/2 pounds per

square inch (psi) (3.45 kilopascals [kPa]). If the test

pressure is equal to or less than 1/2 psi (3.45 kPa),

close the manual shutoff valve on the heater during

the piping pressure test.

Table 5.  Gas Supply Pressure Requirements

Supply Pressure

Natural Gas

Propane Gas

Water Column

  in.    (kPa)

 in.    (kPa)

Minimum

6

(1.5)

11

(2.8)

Maximum

10.5(2.7)

14

(3.5

)

Figure 7.  The Proper Design for a Sediment Trap/Drip

   Leg.

Table 4.   Natural Gas Pipe Size Requirements

Distance from Gas Meter

0-50 feet

50-100 feet

100-200 feet

Heater

(0-15 m)

(15-30 m)

(30-60 m)

Size

in.

in.

in.

250

1

1-1/4

1-1/4

400

1-1/4

1-1/2

1-1/2

Notes:

1. These numbers are for natural gas (0.65 Sp. Gr.) and

are based on 1/2 inch (3.45 kPa) water column pressure

drop.  Check supply pressure with a manometer, and

local code requirements for variations.  

For liquefied

petroleum gas, reduce pipe diameter one size, but

maintain a 3/4 inch minimum diameter.

2. Check  supply  pressure  and  local  code  requirements

before preceding with work.

10. If the gas supply pressure is less than required, check

for undersized pipe between the meter and the heater,

a restrictive fitting, or an undersized gas meter. Gas

supply pressures to the heater, when it is operating,

are listed in Table 5.

NOTE

: The maximum inlet gas pressure must not

exceed the specified value. The minimum value listed is

for the purpose of proper heater operation. Refer to Table

11. To connect the gas supply line to the heater's gas

valve, you must first install a steel elbow (supplied

with the heater in the installation and instruction

box). Screw the elbow into the inlet side of the gas

valve. The heater is designed so that the gas supply

line may enter through either side of the heater. Hand

tighten the elbow until the desired orientation is

achieved.

CAUTION

Do not over tighten the elbow.  Over tightening

will crack the gas valve. Do not use teflon tape

to wrap the elbow threads.

Manual Shutoff

Valve

Gas Supply

Inlet

To

Equipment

Inlet

Union

Cap

T-Fitting

3" Min.

Nipple

Содержание Laars LT250

Страница 1: ...t causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not...

Страница 2: ...ef Valve 14 2I 5 Automatic Chlorinators Chemical Feeders 15 2J Start Up and Adjustment 15 2J 1 Normal Operation 15 2J 2 Start Up 15 2J 3 Gas Pressure 16 2J 4 Adjustment of Water Pressure Switch 16 2J...

Страница 3: ...uded in a plastic bag inside the heater and on the back cover of this manual The home owner should fill out the warranty registration card included in the plastic bag and return it to Waterpik Technol...

Страница 4: ...roper operation 2C Heater Location 2C 1 Installation Information The LX and LT can be installed outdoors or indoors as outlined in later sections In either case location must be selected with consider...

Страница 5: ...so apply such as provision of ample uncontaminated air for combustion and ventilation 2F Indoor Installation 2F 1 Preparation of Heater for Indoor Installation If the LX or LT is to be installed indoo...

Страница 6: ...Codes for Gas Appliances CAN 1 B149 1 2 Undersize pipe can result in inadequate venting and oversize pipe can result in vent condensation In either case the result can be release of combustion produc...

Страница 7: ...be a Category I Fan Assisted appliance They are intended for standard vertical venting per tables provided in most local codes for Category I Fan Assisted appliances If the local code does not include...

Страница 8: ...ximum 10 5 2 7 14 3 5 Figure 7 The Proper Design for a Sediment Trap Drip Leg Table 4 Natural Gas Pipe Size Requirements Distance from Gas Meter 0 50 feet 50 100 feet 100 200 feet Heater 0 15 m 15 30...

Страница 9: ...MP SENSOR J4 1 J4 2 0 6 1 6 1 7 5 7 5 32 5 6285 5 5 3 5 5 3 5 5 5 3 5 5 3 5 5 5 5 5 5 5 5 5 5 2 8 1 6 5 5 2 8 1 6 5 1 6 5 9 1 1 7 9 3 6 3 6 9 1 7 9 1 7 3 6 3 6 0 9 0 9 0 9 0 9 7 5 3 5 6 6 8 5 6 7 0 7...

Страница 10: ...connected to either tab on the terminal block the connections are not polarity sensitive Plug the fifteen pin connector into the receptacle The connector is keyed so it will fit in only one orientatio...

Страница 11: ...it A number will appear on the display for approximately 5 seconds This first number can be ignored After the first number disappears a second number will appear in the display window It will consist...

Страница 12: ...r is disabled The heater functions can be controlled only at the RS unit However sensor data is displayed at both the heater and the RS unit To temporarily use the heater controls use a thin object to...

Страница 13: ...ntrol panel There are quick disconnects at the end of the wires 15 Remove the inlet outlet header side cover plate located under the inlet outlet header There are four philips head screws one in each...

Страница 14: ...one in each corner 26 Route the wires that attach to the temperature sensor along the copper siphon loop back to the right side of the heater Reconnect the wires to the tabs on the back of the control...

Страница 15: ...e top of the heater Be careful not to pinch any wires Replace the two screws on the bottom flange to hold the cover in place 47 Replace the front panel door 2I 2 Pool Spa Piping Systems Figure 15 illu...

Страница 16: ...Technologies PRV kit into the blind threaded hole on the top of the inlet outlet header 2 Using the countersink in the center of the blind hole as a guide drill a 1 4 inch hole through the plastic 3 O...

Страница 17: ...ton until the indicator on the LCD screen aligns with OFF Now press and release the button again until the indicator on the LCD screen aligns with the desired setting either POOL or SPA To reset the m...

Страница 18: ...f Setting the switch to close at too low of a flow can damage the appliance Do not operate this heater outdoors at temperatures below 20 degrees Fahrenheit F 7 degrees Celsius C 2J 2 Start up Confirm...

Страница 19: ...ow even though flow through the filter system will vary depending on how dirty the filter is For most installations an external bypass valve is not needed in the heater water piping This is due to the...

Страница 20: ...from this reading This difference is the temperature rise Refer to Table 8 If your measured temperature rise is within the range designated for your heater skip steps 6 through 8 6 Locate the bypass a...

Страница 21: ...n there is water flowing through the heater the filter pump is on the water temperature is displayed in the right most of two bar graphs in the center of the screen This bar graph is labeled as Water...

Страница 22: ...he heater is OFF It is now necessary to set the thermostat to the desired pool or spa setting 3B 3 Setting Pool and Spa Temps Changing from Fahrenheit to Celsius The Model LX heater displays temperatu...

Страница 23: ...switch 1 Broken split pinched or disconnected fan switch tubing 1 Check tubing and replace if necessary 2 Fan not operating 2 Correct fault or replace fan Refer to qualified service personnel 3 Fan ru...

Страница 24: ...lve control knob counterclockwise to ON see Figure 22 5 Replace the heater door 6 Turn on electrical power to the heater 7 Turn on the filter pump 8 Set the heater controls to the SPA position mode If...

Страница 25: ...to next step 8 Turn gas control knob counterclockwise to ON A This appliance does not have a pilot light It is equipped with an ignition device which automatically lights the heater Do NOT try to lig...

Страница 26: ...e week It should be reset to the 78 F 26 C level before expected usage keeping in mind to allow enough lead time for the water to reach the desired temperature 3D 2a Spa Water Chemistry Maintaining sa...

Страница 27: ...ater is not going to be used for a long period of time shut it down completely following the instructions in Section 3C 2 Shutdown or the lighting and shutdown instructions posted inside the heater 3G...

Страница 28: ...erature control g Control circuit fuse 6 Perform a temperature rise test in accordance with Section 2J 5 7 If the heater is equipped with a pressure relief valve clean any accumulated corrosion and ma...

Страница 29: ...0444900 33 RetainerBracket Temp Sensor All 10447300 34 Screw RetainerBracket All F0009100 35 IgnitionControl All R0328800 36 Pressure Switch Assy All R0334500 37 Pressure Switch 2 psi All R0013200 38...

Страница 30: ...EE NEXT PAGE FOR DETAIL 20 21 22 23 25 SEE NEXT PAGE FOR DETAIL 44 54 55 57 SEE NEXT PAGE FOR DETAIL 58 59 60 60 61 63 64 65 66 67 68 69 70 71 72 73 10 9 SEE NEXT PAGE FOR DETAIL 45 24 62 74 56 36 38...

Страница 31: ...LX and LT Pool Heaters Page 29 2 3 4 5 7 8 11 11 12 16 17 15 18 19 14 35 27 29 37 42 40 41 52 53 51 32 31 30 34 33 43 43 6 5C 2 Detail View 77...

Страница 32: ...orized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing chemicals upstream of th...

Отзывы: