Jandy Laars LT250 Скачать руководство пользователя страница 19

LX and LT Pool Heaters

Page 17

To adjust the pressure switch, proceed as follows (see

Figure 19).

The pool filter must be clean before making this

adjustment. The heater does not have to be firing.
1.

Set the heater control to the "OFF" position.

2.

Start the filter pump and confirm by means of an

voltmeter that the pressure switch closes (if the

switch fails to close, replace it with a switch which

has a lower minimum setting).

3.

Set the heater control to either 'Pool' or 'Spa'. Heater

should start.

4.

Pry out the top rubber dirt plug on the pressure

switch.

5.

Use a 7/32 inch Allen wrench to turn the adjustment

screw very slowly clockwise until the heater goes off.

6.

Slowly turn the pressure switch adjustment screw

counterclockwise

 one-quarter turn. The heater

should come back on.

7.

Check the adjustment by turning the filter pump OFF.

The heater fan will continue to run but the burners

should shut off immediately. If they do not, restart the

filter pump and repeat Steps 6 and 7. Check the

adjustment again.

8.

Return the pool temperature control to the desired

temperature.
It may be necessary to repeat these steps to get a

proper setting. The switch must be set so that the heater

will not fire unless the pump is running. If a proper setting

cannot be reached, contact the factory service department.

2J-5. Water Temperature Rise

The Laars LX and LT pool heaters have an internal

bypass which accommodates a wide range of water flow.

The bypass is easily adjustable to change the temperature

rise for optimum performance and length of heater life.

The bypass assures constant heat exchanger flow even

though flow through the filter system will vary depending

on how dirty the filter is.

For most installations, an external bypass valve is

not needed in the heater water piping. This is due to the

large size of the heater's internal bypass valve. If the pump

flow rate is known to significantly exceed 125 gpm

(7.9 l/s), an external bypass may be needed to assure

proper heater operation.

Water flow should be confirmed upon start-up of the

heater and in most servicing situations. If the flow is not

normal, corrections must be made to the pool system. Flow

is evaluated by determining the water temperature rise

through the heat exchanger.

Before checking the temperature rise, make sure that

the pool filter is clean. If necessary, clean all components

of the filter system.  Temperature rise is measured in the

outlet of the far-right tubes when facing the inlet/outlet

water heater. To measure the temperature rise, turn off the

filter pump and remove the plastic plug to the right of, and

just below the level of the outlet water pipe. This is

mounted flush with the heater jacket (See Figure 20). With

the plug removed, install the special thread adapter and

"Pete’s" plug fitting and insert a pocket thermometer.

The internal bypass can be adjusted by means of a

screw on the right hand side of the header.  To adjust the

temperature rise to within the ranges specified in table 8,

proceed as follows.

1.

If the piping system has an external bypass valve,

close it.

2.

Set the heater's control panel to the "Off" position.

3.

Start the filter pump.

4.

After three minutes, note and record the thermometer

reading.  This is the pool water temperature.

Pry off cap

to adjust

Figure 19. Adjustment of Pressure Switch.

THERMOMETER

WITH PETE'S

PLUG

Figure 20. Temperature Rise Measurement

BYPASS

ADJUSTMENT

SCREW

Содержание Laars LT250

Страница 1: ...t causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not...

Страница 2: ...ef Valve 14 2I 5 Automatic Chlorinators Chemical Feeders 15 2J Start Up and Adjustment 15 2J 1 Normal Operation 15 2J 2 Start Up 15 2J 3 Gas Pressure 16 2J 4 Adjustment of Water Pressure Switch 16 2J...

Страница 3: ...uded in a plastic bag inside the heater and on the back cover of this manual The home owner should fill out the warranty registration card included in the plastic bag and return it to Waterpik Technol...

Страница 4: ...roper operation 2C Heater Location 2C 1 Installation Information The LX and LT can be installed outdoors or indoors as outlined in later sections In either case location must be selected with consider...

Страница 5: ...so apply such as provision of ample uncontaminated air for combustion and ventilation 2F Indoor Installation 2F 1 Preparation of Heater for Indoor Installation If the LX or LT is to be installed indoo...

Страница 6: ...Codes for Gas Appliances CAN 1 B149 1 2 Undersize pipe can result in inadequate venting and oversize pipe can result in vent condensation In either case the result can be release of combustion produc...

Страница 7: ...be a Category I Fan Assisted appliance They are intended for standard vertical venting per tables provided in most local codes for Category I Fan Assisted appliances If the local code does not include...

Страница 8: ...ximum 10 5 2 7 14 3 5 Figure 7 The Proper Design for a Sediment Trap Drip Leg Table 4 Natural Gas Pipe Size Requirements Distance from Gas Meter 0 50 feet 50 100 feet 100 200 feet Heater 0 15 m 15 30...

Страница 9: ...MP SENSOR J4 1 J4 2 0 6 1 6 1 7 5 7 5 32 5 6285 5 5 3 5 5 3 5 5 5 3 5 5 3 5 5 5 5 5 5 5 5 5 5 2 8 1 6 5 5 2 8 1 6 5 1 6 5 9 1 1 7 9 3 6 3 6 9 1 7 9 1 7 3 6 3 6 0 9 0 9 0 9 0 9 7 5 3 5 6 6 8 5 6 7 0 7...

Страница 10: ...connected to either tab on the terminal block the connections are not polarity sensitive Plug the fifteen pin connector into the receptacle The connector is keyed so it will fit in only one orientatio...

Страница 11: ...it A number will appear on the display for approximately 5 seconds This first number can be ignored After the first number disappears a second number will appear in the display window It will consist...

Страница 12: ...r is disabled The heater functions can be controlled only at the RS unit However sensor data is displayed at both the heater and the RS unit To temporarily use the heater controls use a thin object to...

Страница 13: ...ntrol panel There are quick disconnects at the end of the wires 15 Remove the inlet outlet header side cover plate located under the inlet outlet header There are four philips head screws one in each...

Страница 14: ...one in each corner 26 Route the wires that attach to the temperature sensor along the copper siphon loop back to the right side of the heater Reconnect the wires to the tabs on the back of the control...

Страница 15: ...e top of the heater Be careful not to pinch any wires Replace the two screws on the bottom flange to hold the cover in place 47 Replace the front panel door 2I 2 Pool Spa Piping Systems Figure 15 illu...

Страница 16: ...Technologies PRV kit into the blind threaded hole on the top of the inlet outlet header 2 Using the countersink in the center of the blind hole as a guide drill a 1 4 inch hole through the plastic 3 O...

Страница 17: ...ton until the indicator on the LCD screen aligns with OFF Now press and release the button again until the indicator on the LCD screen aligns with the desired setting either POOL or SPA To reset the m...

Страница 18: ...f Setting the switch to close at too low of a flow can damage the appliance Do not operate this heater outdoors at temperatures below 20 degrees Fahrenheit F 7 degrees Celsius C 2J 2 Start up Confirm...

Страница 19: ...ow even though flow through the filter system will vary depending on how dirty the filter is For most installations an external bypass valve is not needed in the heater water piping This is due to the...

Страница 20: ...from this reading This difference is the temperature rise Refer to Table 8 If your measured temperature rise is within the range designated for your heater skip steps 6 through 8 6 Locate the bypass a...

Страница 21: ...n there is water flowing through the heater the filter pump is on the water temperature is displayed in the right most of two bar graphs in the center of the screen This bar graph is labeled as Water...

Страница 22: ...he heater is OFF It is now necessary to set the thermostat to the desired pool or spa setting 3B 3 Setting Pool and Spa Temps Changing from Fahrenheit to Celsius The Model LX heater displays temperatu...

Страница 23: ...switch 1 Broken split pinched or disconnected fan switch tubing 1 Check tubing and replace if necessary 2 Fan not operating 2 Correct fault or replace fan Refer to qualified service personnel 3 Fan ru...

Страница 24: ...lve control knob counterclockwise to ON see Figure 22 5 Replace the heater door 6 Turn on electrical power to the heater 7 Turn on the filter pump 8 Set the heater controls to the SPA position mode If...

Страница 25: ...to next step 8 Turn gas control knob counterclockwise to ON A This appliance does not have a pilot light It is equipped with an ignition device which automatically lights the heater Do NOT try to lig...

Страница 26: ...e week It should be reset to the 78 F 26 C level before expected usage keeping in mind to allow enough lead time for the water to reach the desired temperature 3D 2a Spa Water Chemistry Maintaining sa...

Страница 27: ...ater is not going to be used for a long period of time shut it down completely following the instructions in Section 3C 2 Shutdown or the lighting and shutdown instructions posted inside the heater 3G...

Страница 28: ...erature control g Control circuit fuse 6 Perform a temperature rise test in accordance with Section 2J 5 7 If the heater is equipped with a pressure relief valve clean any accumulated corrosion and ma...

Страница 29: ...0444900 33 RetainerBracket Temp Sensor All 10447300 34 Screw RetainerBracket All F0009100 35 IgnitionControl All R0328800 36 Pressure Switch Assy All R0334500 37 Pressure Switch 2 psi All R0013200 38...

Страница 30: ...EE NEXT PAGE FOR DETAIL 20 21 22 23 25 SEE NEXT PAGE FOR DETAIL 44 54 55 57 SEE NEXT PAGE FOR DETAIL 58 59 60 60 61 63 64 65 66 67 68 69 70 71 72 73 10 9 SEE NEXT PAGE FOR DETAIL 45 24 62 74 56 36 38...

Страница 31: ...LX and LT Pool Heaters Page 29 2 3 4 5 7 8 11 11 12 16 17 15 18 19 14 35 27 29 37 42 40 41 52 53 51 32 31 30 34 33 43 43 6 5C 2 Detail View 77...

Страница 32: ...orized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing chemicals upstream of th...

Отзывы: