Jandy Laars LT250 Скачать руководство пользователя страница 18

Page 16

side of the valve. The pressure will be zero when the heater

is not running. When the heater is operating the manifold

gas pressure should be 4.0" wc for natural gas and 9.0" wc

for LP within .2" wc. To adjust the manifold gas pressure,

first remove the slotted cap next to the inlet pressure port

on the inlet side of the gas valve. Under the slotted cap is a

slotted plastic screw which increases the manifold pressure

when turned clockwise and decreases the manifold pressure

when turned counterclockwise.  After measurements, and

adjustments if necessary, have been made, make sure to

replace the 1/8" NPT gas valve plugs on the inlet and

manifold pressure ports, and the cap on the manifold

pressure adjustment screw.  It is extremely important to

replace these parts before leaving the installation.  Failure to

do so can result in damage to property or injury or death.

With the heater firing

, the pressure must be within the

range shown in Table 7. Also check the pressure with the

heater off.

Table 7. Gas Supply Pressure Requirements

Supply Pressure

  Minimum

    Maximum

Natural Gas

6.0 Inches WC

  11.0 Inches WC

(1.5 kPa)

  (2.8 kPa)

LP Gas

10.5 Inches WC

  14.0 Inches WC

(2.7 kPa)

  (3.5 kPa)

Manifold Pressure    Nominal

Natural Gas

4.0 Inches WC (1.0 kPa)

LP Gas

9.0 Inches WC (2.3 kPa)

2J-4. Adjustment of Water Pressure

Switch

If the heater is installed in line with a two speed

pump, the pressure switch 

MUST

 be adjusted to prevent

the heater from firing on low-speed or low-flow pump

operation. The pressure switch is preset at the factory for

normal pool installations. Do not adjust it unless the

heater's water connections are more than three feet above

or below the pool surface. If they are not in this range, the

pressure switch must be adjusted. This can be done in the

field if the water connections are no more than six feet

above the pool surface or no more than ten feet below it.

For other situations, contact a Waterpik Technologies

representative.

The pressure switch should be adjusted to turn

the heater off when the pump is off. Setting

the switch to close at too low of a flow can

damage the appliance.

Do not operate this heater outdoors at

temperatures below 20 degrees Fahrenheit

(°F)  (-7 degrees Celsius [°C]).

2J-2. Start-up

Confirm that pool water is flowing normally through

the pool system and equipment. Start the heater in

accordance with the Operating Instructions section of this

manual, with particular attention to the lighting and

shutdown instructions and temperature control operation.

The heater may not start on the first try. Air in the

gas line or other start-up situations may cause it to recycle.

It will lock out if ignition is not achieved in three attempts.

On the LX model heater, to provide three additional

attempts, press and release the mode button until the

indicator on the LCD screen aligns with "OFF". Now press

and release the button again until the indicator on the

LCD screen aligns with the desired setting, either "POOL"

or "SPA".

To reset the cycle on the model LT press and release

the mode button until the indicator lights for the "SPA"

and "POOL" settings are off. Then press and release it

again until the indicator light for the desired setting is

back on..

When the heater starts, immediately feel the outlet

header of the heater to confirm that there is adequate water

flow. The header should not be hot. Normally, water

temperature will rise only a few degrees as it passes

through the heater, and a “hot” header or pipe indicates

low water flow.

When the heater is fired for the first time, the

combustion chamber refractory binder material

is driven out by the heat of the flame. White

smoke and/or sharp odors may be emitted

from the vent during this period. Do not inhale

combustion product fumes at any time, and

especially when these fumes are being

emitted. This “burn-in” period will last only a

few minutes.

2J-3. Gas Pressure

Confirm that gas supply pressure is correct. If the

gas supply pressure is less than required, check for

undersized pipe between the meter and the heater, a

restrictive fitting, or an undersized gas meter. Gas supply

pressures to the heater, when it is operating, are listed in

Table 7.

The manifold pressure may be checked by

connecting a manometer to the pressure port on the outlet

WARNING

WARNING

CAUTION

Содержание Laars LT250

Страница 1: ...t causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not...

Страница 2: ...ef Valve 14 2I 5 Automatic Chlorinators Chemical Feeders 15 2J Start Up and Adjustment 15 2J 1 Normal Operation 15 2J 2 Start Up 15 2J 3 Gas Pressure 16 2J 4 Adjustment of Water Pressure Switch 16 2J...

Страница 3: ...uded in a plastic bag inside the heater and on the back cover of this manual The home owner should fill out the warranty registration card included in the plastic bag and return it to Waterpik Technol...

Страница 4: ...roper operation 2C Heater Location 2C 1 Installation Information The LX and LT can be installed outdoors or indoors as outlined in later sections In either case location must be selected with consider...

Страница 5: ...so apply such as provision of ample uncontaminated air for combustion and ventilation 2F Indoor Installation 2F 1 Preparation of Heater for Indoor Installation If the LX or LT is to be installed indoo...

Страница 6: ...Codes for Gas Appliances CAN 1 B149 1 2 Undersize pipe can result in inadequate venting and oversize pipe can result in vent condensation In either case the result can be release of combustion produc...

Страница 7: ...be a Category I Fan Assisted appliance They are intended for standard vertical venting per tables provided in most local codes for Category I Fan Assisted appliances If the local code does not include...

Страница 8: ...ximum 10 5 2 7 14 3 5 Figure 7 The Proper Design for a Sediment Trap Drip Leg Table 4 Natural Gas Pipe Size Requirements Distance from Gas Meter 0 50 feet 50 100 feet 100 200 feet Heater 0 15 m 15 30...

Страница 9: ...MP SENSOR J4 1 J4 2 0 6 1 6 1 7 5 7 5 32 5 6285 5 5 3 5 5 3 5 5 5 3 5 5 3 5 5 5 5 5 5 5 5 5 5 2 8 1 6 5 5 2 8 1 6 5 1 6 5 9 1 1 7 9 3 6 3 6 9 1 7 9 1 7 3 6 3 6 0 9 0 9 0 9 0 9 7 5 3 5 6 6 8 5 6 7 0 7...

Страница 10: ...connected to either tab on the terminal block the connections are not polarity sensitive Plug the fifteen pin connector into the receptacle The connector is keyed so it will fit in only one orientatio...

Страница 11: ...it A number will appear on the display for approximately 5 seconds This first number can be ignored After the first number disappears a second number will appear in the display window It will consist...

Страница 12: ...r is disabled The heater functions can be controlled only at the RS unit However sensor data is displayed at both the heater and the RS unit To temporarily use the heater controls use a thin object to...

Страница 13: ...ntrol panel There are quick disconnects at the end of the wires 15 Remove the inlet outlet header side cover plate located under the inlet outlet header There are four philips head screws one in each...

Страница 14: ...one in each corner 26 Route the wires that attach to the temperature sensor along the copper siphon loop back to the right side of the heater Reconnect the wires to the tabs on the back of the control...

Страница 15: ...e top of the heater Be careful not to pinch any wires Replace the two screws on the bottom flange to hold the cover in place 47 Replace the front panel door 2I 2 Pool Spa Piping Systems Figure 15 illu...

Страница 16: ...Technologies PRV kit into the blind threaded hole on the top of the inlet outlet header 2 Using the countersink in the center of the blind hole as a guide drill a 1 4 inch hole through the plastic 3 O...

Страница 17: ...ton until the indicator on the LCD screen aligns with OFF Now press and release the button again until the indicator on the LCD screen aligns with the desired setting either POOL or SPA To reset the m...

Страница 18: ...f Setting the switch to close at too low of a flow can damage the appliance Do not operate this heater outdoors at temperatures below 20 degrees Fahrenheit F 7 degrees Celsius C 2J 2 Start up Confirm...

Страница 19: ...ow even though flow through the filter system will vary depending on how dirty the filter is For most installations an external bypass valve is not needed in the heater water piping This is due to the...

Страница 20: ...from this reading This difference is the temperature rise Refer to Table 8 If your measured temperature rise is within the range designated for your heater skip steps 6 through 8 6 Locate the bypass a...

Страница 21: ...n there is water flowing through the heater the filter pump is on the water temperature is displayed in the right most of two bar graphs in the center of the screen This bar graph is labeled as Water...

Страница 22: ...he heater is OFF It is now necessary to set the thermostat to the desired pool or spa setting 3B 3 Setting Pool and Spa Temps Changing from Fahrenheit to Celsius The Model LX heater displays temperatu...

Страница 23: ...switch 1 Broken split pinched or disconnected fan switch tubing 1 Check tubing and replace if necessary 2 Fan not operating 2 Correct fault or replace fan Refer to qualified service personnel 3 Fan ru...

Страница 24: ...lve control knob counterclockwise to ON see Figure 22 5 Replace the heater door 6 Turn on electrical power to the heater 7 Turn on the filter pump 8 Set the heater controls to the SPA position mode If...

Страница 25: ...to next step 8 Turn gas control knob counterclockwise to ON A This appliance does not have a pilot light It is equipped with an ignition device which automatically lights the heater Do NOT try to lig...

Страница 26: ...e week It should be reset to the 78 F 26 C level before expected usage keeping in mind to allow enough lead time for the water to reach the desired temperature 3D 2a Spa Water Chemistry Maintaining sa...

Страница 27: ...ater is not going to be used for a long period of time shut it down completely following the instructions in Section 3C 2 Shutdown or the lighting and shutdown instructions posted inside the heater 3G...

Страница 28: ...erature control g Control circuit fuse 6 Perform a temperature rise test in accordance with Section 2J 5 7 If the heater is equipped with a pressure relief valve clean any accumulated corrosion and ma...

Страница 29: ...0444900 33 RetainerBracket Temp Sensor All 10447300 34 Screw RetainerBracket All F0009100 35 IgnitionControl All R0328800 36 Pressure Switch Assy All R0334500 37 Pressure Switch 2 psi All R0013200 38...

Страница 30: ...EE NEXT PAGE FOR DETAIL 20 21 22 23 25 SEE NEXT PAGE FOR DETAIL 44 54 55 57 SEE NEXT PAGE FOR DETAIL 58 59 60 60 61 63 64 65 66 67 68 69 70 71 72 73 10 9 SEE NEXT PAGE FOR DETAIL 45 24 62 74 56 36 38...

Страница 31: ...LX and LT Pool Heaters Page 29 2 3 4 5 7 8 11 11 12 16 17 15 18 19 14 35 27 29 37 42 40 41 52 53 51 32 31 30 34 33 43 43 6 5C 2 Detail View 77...

Страница 32: ...orized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing chemicals upstream of th...

Отзывы: