Jandy ePump Скачать руководство пользователя страница 6

Page 6

Section 2. Installation of the User 

Interface

2.1 Introduction

This document provides general instructions to install the 
user interface for use with the Jandy ePump

TM

 variable speed 

pump. The user interface can be mounted to an electrical gang 
box (single, double, or triple) or to a flat wall.

The instructions have been written with safety as the priority, 
and must be followed exactly. Read through the instructions 
completely before starting the procedure.

2.2 

The User Interface Panel

The user interface panel provides both timed and manual 
speed controls for the Jandy ePump

TM

  

Variable Speed Pump.

Four speed presets are directly available on the panel, while 
four (4) additional presets may be accessed via the 

MENU

 

key.  

The up and down keys are used to adjust the pump speed. 
Speed is saved as it is adjusted. No further action is required 
to save the new speed setting after adjustment. The selected 
speed can be saved and assigned to one of the speed buttons.

As shown in Figure 1, preset speed "

œ

" is assigned to 

the "eStar" feature. Hence, it is intended to be assigned 
an energy-efficient filtration speed, as determined by the 
installer.

Figure 1. 

Jandy ePump

TM 

Variable Speed Pump 

User Interface Panel

LCD Display

Preset Speed

Buttons

Menu Button

LED Lights

Up/Down

Arrow Keys

2

3

4

PRESS PRESET OR MENU

12:00AM         PUMP IS OFF

ePUMP

MENU

eStar Button

Figure 2. 

User Interface Components

2.3 

The User Interface Components

The ePump™ user interface assembly (See Figure 2) contains 
the following components:

1. User 

Interface

2. Mounting 

Gasket

3. Backplate

4. Round 

Seal

5. 

Six (6) Screws

6. Plastic 

Film

Additional materials are required for the installation of the 
user interface and must be supplied by the installer:

1.  A cable to connect the pump to the remotely mounted 

user interface, minimum size of 22 AWG (Jandy part 
number 4278). This cable will need to have four (4) 
conductors and be able to handle 24V control signals. 
This cable should be rated for the particular installation 
(for example: outdoor, UV resistant, direct burial, 
etc.) and should conform to all applicable codes and 
regulations. (A suitable cable is included in the JEP 
Series ePump water pumps.)

2.  A minimum of two (2) fasteners to mount the user 

interface back plate to a wall or electrical box. The 
fasteners should be suitable for the surface where the 
user interface is to be remotely mounted.

3. A 

high-voltage

 

disconnect switch, as required by the 

National Electric Code (NEC), within line of sight of the 
pump.

2.4 

Installation of the Backplate onto an 
Electrical Box

 

 CAUTION

Do not expose the user interface to direct sunlight. Too 
much direct sunlight will darken the LCD screen, and it 
will no longer be readable.

1.  Turn off the pump at the control panel.

2.  Turn off all electrical power to the pump at the main 

junction box or at the circuit breaker providing electrical 
power to the pump.

  WARNING

ELECTRICAL SHOCK HAZARD

Turn off all switches and the main breaker in the ePump™ 
electrical circuit before starting the procedure. Failure to 
comply may cause a shock hazard resulting in severe 
personal injury or death.

3.  Drill out the plastic film covering the backplate screw 

holes. See Figure 2.

4.  Secure the backplate to the box using the screws that 

came with the electrical box. 

Screws (6)

User Interface

Gasket

Backplate

Round Seal

Plastic Film

Screws
(not supplied with kit)

Breakout tabs

Содержание ePump

Страница 1: ...serviced by a professional pool spa service technician The procedures in this manual must be followed exactly Failure to follow warning notices and instructions may result in property damage serious i...

Страница 2: ......

Страница 3: ...d Stop 9 3 4 Pump Speed Setting 9 3 5 Timeclock Setup and Operation 10 Section 4 Service Setup Options 11 4 1 Entering Service Setup 11 4 2 Minimum and Maximum Pump Speeds 11 4 3 Load Defaults 11 4 4...

Страница 4: ...broken or missing Never replace a suction fitting with one rated less than the flow rate marked on the equipment assembly WARNING To Reduce the Risk of Injury a The water in a spa should never exceed...

Страница 5: ...trant dans une cuve de relaxation et en sortant Pour viter l vanouissement et la noyade ventuelle ne prendre ni drougue ni alcool avant d utiliser une cuve de relaxation ni quand on s y trouve Les fem...

Страница 6: ...crews 6 Plastic Film Additional materials are required for the installation of the user interface and must be supplied by the installer 1 A cable to connect the pump to the remotely mounted user inter...

Страница 7: ...ump electrical circuit before starting the procedure Failure to comply may cause a shock hazard resulting in severe personal injury or death 2 Remove the cover of the pump junction box 3 Feed the RS 4...

Страница 8: ...o comply may cause a shock hazard resulting in severe personal injury or death 2 Install the normally closed reman s switch to the timeclock assembly See timeclock manufacturer s instructions for deta...

Страница 9: ...rted from the controller Manual operation of speeds eStar through 4 differs from manual operation of speeds 5 through 8 NOTE When starting the pump the pump will first run at the priming speed for the...

Страница 10: ...UN mode 2 3 4 ePUMP MENU 2 PRESET 2 TIMECLOCK ENABLE 3 5 2 Timeclock Operation When the pump is stopped the associated green LED will illuminate indicating a timeclock program is enabled for that spee...

Страница 11: ...enu press and hold MENU then press and hold the and preset 4 keys Hold all three 3 keys down for five 5 seconds To exit press any preset button 2 3 4 ePUMP MENU PRESS PRESET OR MENU 12 00AM PUMP IS OF...

Страница 12: ...ing the arrow keys set the priming speed to the desired value Press MENU to accept and store 2 3 4 PRIMING SPEED RPM 3450 ePUMP MENU To set priming duration select PRIMING DURATION using the arrow key...

Страница 13: ...s time the ePump controller does not support other types of pumps Section 5 User Set Up Options NOTE The ePumpTM user interface must be in the OFF mode before entering the user setup mode While in set...

Страница 14: ...keys select the desired operating mode for the display backlight LIGHT OFF Turn off display backlight LIGHT ON Turn on display backlight 2 MIN TIMEOUT Turn on display backlight with automatic turn of...

Страница 15: ...s not affected when LOAD DEFAULTS is executed 8 Key that is pressed to wake up display is also acted upon 9 Press and hold MENU eStar and 4 simultaneously for 5 seconds to enter 10 Setting not saved i...

Страница 16: ...lished minimum and maximum specifications 7 Use of non factory authorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizin...

Отзывы: