Page 17
NOTE
One end of the wiring reserved to run into
the conduit connection labeled “Low Voltage
Connection”, located on the lower right hand
side of the heat pump (see Figures 12 and 14).
2. Run the wires from the Heat Pump control panel
through the wiring conduit located on the outer
right hand side of the Heat Pump.
3. In the AquaLink Power Center, connect the Heat
Pump to a standard relay, then connect the relay
to the solar pump output on the PCB. Set the time
to 11:59 PM; at 12:00 AM, the AquaLink RS
will auto-relabel Solar as Heat Pump. Otherwise,
the AquaLink RS will auto-relabel Solar as Heat
Pump within 24 hours.
4. The Solar Button will activate the heat pump/
chiller and the Pool and/or Spa Heater Buttons will
activate the gas heater. In this manner the pool or
spa can be heated or chilled by the heat pump, the
gas heater or both.
Gas Heater
Heat Pump/Chiller #2
Service/Wiring
Cover Panel
4 3 2 1
6 5 4 3 2 1
10 9 8 7 6 5 4 3 2 1
Battery
(9Volt)
Standard
High
Voltage
Relay
Heat Pump/Chiller #1
Green- Enabled
Red- On
Gas Heater Connections
Terminals 1 and 2
Fireman's
Switch
From Fusible
Link
To Pressure
Switch
LED
will not
come on
for Heat
Pump
2.2K Ohms Resistor
in Solar Sensor
Terminals for Heat
Pump/Chiller
Figure 15. AquaLink RS to AE-Ti Heat Pump/Chiller Wiring
Low Voltage
Wiring to Low
Voltage Port
on Heat Pump
Service/Wiring
Cover Panel
Port for Low
Voltage Wires
Port for Low
Voltage Wires