Page 15
4.2 Main
Power
Electrical wiring to the heat pump must be in
accordance with the latest edition of the National
Electric Code (NEC), ANSI/National Fire Protection
Association (NFPA) 70 in the United States, and in
Canada, the Canadian Electrical Code (CEC) C22.1,
unless local code requirements indicate otherwise.
The heat pumps come factory-wired intended for
use with either 208/230 VAC, 60 Hz field electrical
supply depending on the model. See the rating plate for
the electrical specifications. All wiring must be done by
a certified electrician.
The following is the procedure to wire the AE-Ti
to the electrical source specified on the Rating Plate:
1. Be sure the power to the circuit for the heat pump
is turned off.
2. Remove the 5 screws that attach the service/access
panel to the heat pump unit (see Figure 12).
3. Electrical supply lines must be run through
watertight conduit. Run the wires and conduit from
the power source and connect them to the conduit
connection labeled “High Voltage Connection” on
the right side of the heat pump. See Figure 12 for
connection location.
4. Connect the wires to the terminals on the main
contactor as shown in the wiring diagram.
5. Connect the ground wire to the ground lug
provided in the electrical compartment.
6. Replace the service access panel and replace the
screws to hold it in place.
7. Connect a copper bonding wire (8 AWG) to the
bonding lug on the right side of the heat pump.
4.3 Bonding
PORT FOR TIME
CLOCK OVERRIDE
WIRES
PORT FOR HIGH
VOLTAGE WIRES
PORT FOR LOW
VOLTAGE WIRES
SERVICE ACCESS
PANEL (5 SCREWS)
Figure 12. AE-Ti Heat Pump Front View
CAUTION
This heater must be connected to a bonding
grid with a solid copper wire not smaller in
diameter than 8 ga.
ATTENTION
L’appareil de chauffage doit être connecté à
une grille de mise à la terre par un fi l de cuivre
d’un diamètre de calibre minimal 8.
PRECAUCIÓN
Esta bomba de calor deberá estar conectado
a una rejilla de unión con hilo de cobre sólido,
de un diámetro no inferior a 8 ga.
The National Electrical Code and most other
codes require that all metallic components of a pool
structure, including reinforcing steel, metal fittings,
and above ground equipment be bonded together with
a solid copper conductor not smaller than 8 AWG. The
heat pump, along with pumps and other pool equipment
must be connected to this bonding grid. A bonding lug
is provided on the right hand side of the heat pump to
ensure this requirement is met.