Fault Diagnosis

5-1

 Revision 0.1 – 3 June 1999

FP12  DIMMER

USER MANUAL

5.0

Fault Diagnosis

NOTE

Contact your authorised JANDS Distributor for repairs or servicing.

In Australia refer all repairs to an authorised JANDS service agent or return the
faulty unit in suitable packaging to:

JANDS ELECTRONICS Service Dept,

40 Kent Rd

Mascot NSW 2020

Australia

5.1

Output protection

 

Each of the twelve output circuits is protected by a 10 amp fast-acting thermal/magnetic
circuit breaker. These breakers are designed to pass the rated current, but will disconnect
the output circuit for any overload condition (the larger the overload, the quicker the
disconnection).

 

NOTE: 3-pin GPO outlet sockets are rated at 10 amps. Dimmer channels should
not be loaded beyond the socket capacity.

 

The breakers protect the dimmer’s output devices from short-circuit loads and faulty
wiring looms, and save on expensive dimmer repairs. A tripped circuit breaker indicates a
load fault that requires immediate attention.

If a short-circuit lamp or output cable is plugged into the dimmer, the breaker will trip to
disconnect the fault from the dimmer. In nearly all circumstances, this is quick enough to
prevent damage to the output devices.

In some circumstances however, a triac failure may be experienced, although these
devices are usually quite reliable and robust. If a triac does fail, it will either turn a
channel on to full (triac short-circuit), or turn it off (triac open-circuit). If a triac fault
should occur, that channel may be isolated by tripping that channel’s circuit breaker.

These breakers have been specified for electrical protection, reliability and safety. They
will allow repeated turn-on surges to cold lamps without failure, while still protecting the
triacs. The breakers will interrupt large short-circuit fault currents without damage.

5.2

DMX faults

The FP12 dimmer features an “Output Hold” facility that “remembers” the last received
DMX message. In the event of a cable being unplugged or severed, the FP12 dimmer
rack will continue to output the “Held” DMX levels until a new DMX message is
provided.

The DMX IN LED will “flash” slowly if the DMX signal is removed.

Note that control consoles, when powered down, may transmit spurious DMX data
which can unintentionally cause dimmer channels to turn on. Disconnect mains power
when not in use.

The DMX receiver input is protected against extreme over-voltages across any input pins
and from any input to chassis. The “terminating” resistor is not protected against over-
voltages.

Содержание FP12

Страница 1: ...3...

Страница 2: ...d does not represent a commitment on the part of the vendor JANDS ELECTRONICS PTY LTD shall not be liable for any loss or damage whatsoever arising from the use of information or any error contained i...

Страница 3: ...ring up 3 2 3 4 Connecting loads 3 2 3 5 Connecting DMX 512 input 3 2 3 6 DMX Termination 3 2 3 7 Power up sequence 3 2 4 0 Dimmer Operation 4 1 Operating modes 4 1 4 1 1 DMX mode 4 1 4 1 2 Test mode...

Страница 4: ...0 Technical Data and Specifications 8 1 DMX connector pin outs 8 2 8 2 DMX bank allocations 8 2 8 3 Mains wiring colour codes 8 3 8 4 Internal Mains Wiring 8 3 8 4 1 Normal Three Phase plus Neutral O...

Страница 5: ...ignal to the dimmer is via a standard DMX 512 socket at the front panel while the dimmed outlets and three phase power entry are located on the rear panel Features 12 x 2 4KW dimming channels DMX 512...

Страница 6: ...ensure the fault has been cleared before resetting 3 Bank select switches These switches select the DMX start bank and the Test functions 4 DMX IN LED A red LED indicates the presence of DMX signals...

Страница 7: ...ected by fuses or circuit breakers at not more than the rated maximum The power plug should be connected to an appropriately rated socket outlet The plug s retaining lock ring if present must be screw...

Страница 8: ...P The red DMX IN LED indicates the presence of DMX signals The DMX receiver input is protected against extreme over voltages across any input pins and from any input to chassis The terminating resisto...

Страница 9: ...Channel 25 A FP12 with this setting ignores DMX Channels 1 to 24 and 37 to 512 and only decodes Channels 25 to 36 as it s dimmer information Setting the Selectors to 00 puts the dimmer in a standby s...

Страница 10: ...4 Full 48 Channel 5 Full 49 Channel 6 Full 50 Channel 7 Full 51 Channel 8 Full 52 Channel 9 Full 53 Channel 10 Full 54 Channel 11 Full 55 Channel 12 Full 56 59 12 Step Chase Full Table 4 2 TEST MODE I...

Страница 11: ...er voltage condition is present and the dimmer outputs will be off until the over voltage or over temperature condition is removed 2 When the status LED is on continuously one or more of the following...

Страница 12: ...is quick enough to prevent damage to the output devices In some circumstances however a triac failure may be experienced although these devices are usually quite reliable and robust If a triac does fa...

Страница 13: ...m the dimmer will automatically shut down the output drive The fan will continue to cool the heatsink during the shut down period The electronic shutdown is backed up by a buried cutout which shuts do...

Страница 14: ...ch another console fader Service console Factory service Connect 100W incandescent lamp in parallel Radio interference Faulty EMC filtering Factory service All Channels flicker when dimmed Incorrect D...

Страница 15: ...ntake at the right and air exhaust at the left when viewed from the front All racks must have adequate ventilation for the side to side airflow of the dimmers Fully enclosed racks will cause overheati...

Страница 16: ...immer by disconnecting the power cable or locking off the mains supply isolator Remove the lid Blow clean the fan and internals with compressed air from left to right DO NOT spin the fan with compress...

Страница 17: ...X Input 5 pin AXR male female Test Function Level Individual Channels 100 Group Channels 10 steps LED Indicators DMX IN STATUS Phases A B and C Output Protection 12 x 10 Amp thermal magnetic circuit b...

Страница 18: ...nk allocations BANK CHANNELS BANK CHANNELS 00 Off 22 253 264 01 1 12 23 265 276 02 13 24 24 277 288 03 25 36 25 289 300 04 37 48 26 301 312 05 49 60 27 313 324 06 61 72 28 325 336 07 73 84 29 337 348...

Страница 19: ...mains phases labelled A1 A2 A3 and three poles for the mains neutral N1 N2 N3 The three neutral poles are bridged by a copper link with the incoming mains neutral connected to terminal N2 8 4 2 Single...

Страница 20: ...2 and N1 The third incoming active is connected to terminals A3 and N2 WARNING This connection is ILLEGAL in Australia Europe and the U K This connection renders the output socket s neutral pins LIVE...

Отзывы: