Issue: 01.06.2023
Page 15
FAULT
POSSIBLE CAUSE
CHECK
SOLUTION
Indoor Fan not
running
Is rocker switch on unit switched
on?
If not - switch on
Motor fault
Is there correct voltage at
motor terminals?
If yes - motor faulty. Replace motor
If no - check supply / wiring connections
Check fan capacitor
Replace as required
No display on
controller
Power supply
Is power switched on?
If not - switch on
Is rocker switch on unit switched
on?
If not - switch on
Is there correct voltage at
controller
If yes - controller faulty. Replace
controller
If no - check supply / wiring connections
Power to
controller but no
cooling from unit
Is unit in defrost mode?
Check if defrost LED is
displayed
If yes - all OK. Wait for defrost to end
If no - further checks required
Is unit in cooling mode
(cooling LED displayed)
Is room at required
temperature?
All OK
Room above required
temperature?
Further checks required
Reduced airflow
Fan motor
Is fan rotating slowly?
Further checks required on fan (see
above)
Air inlets blocked
Is anything blocking air inlet
grilles at side of unit
Clear items from around unit
Evaporator coil dirty
Check condition of coil
Clean as necessary
Evaporator coil iced up
Switch off unit and allow to
defrost
Checks required to determine cause of
icing
SYSTEM
Insufficient
cooling
Lack of refrigerant
Is sight glass flashing
continuously?
Leak test system and top up with
refrigerant
Condenser coil dirty
Visual check of coil condition
Clean condenser coil
Lack of ventilation to unit
Any obstructions around unit?
Clear same to ensure good ventilation
Evaporator coil dirty
Visual check of coil condition
Clean evaporator coil
System settings
Controls (inc thermostat) set
correctly?
Adjust as necessary
T.E.V. Superheat
Adjust as necessary
Service valves not open
correctly
Are valves fully open?
Adjust as necessary
Restriction in
piping/component
Is the filter drier blocked?
Sweating/frosting on outlet of
drier indicates a blockage
Replace filter drier
Damage to piping
Replace piping as required
Head pressure
too high
Condenser coil dirty
Visual check of coil condition
Clean condenser coil
System overcharged with
refrigerant
Is head pressure high but liquid
line cool to touch?
Reclaim refrigerant/recharge correctly
Condenser fan not
running
See above (fan will not run)
See above
Lack of ventilation to unit
Any obstructions around unit?
Clear same to ensure good ventilation
System load too high
(overstocked, door open
on coldroom)
Reduce loading
Содержание CellarPlus 70-S1/S3
Страница 1: ...CELLAR PLUS CELLAR COOLER RANGE ISSUE 01 06 2023 CELLAR COOLER RANGE TECHNICAL MANUAL R448A R449A ...
Страница 23: ...Issue 01 06 2023 Page 20 Figure 27 Wiring Diagram BSCU 30 M3 BSCU 35 M3 Figure 28 Wiring Diagram BSCU 40 M3 ...
Страница 26: ...Issue 01 06 2023 Page 23 Figure 30 Declaration of Conformity Outdoor ...
Страница 27: ...Issue 01 06 2023 Page 24 Figure 31 Declaration of Incorporation Indoor ...
Страница 28: ...Issue 01 06 2023 Page 25 Figure 32 Declaration of Incorporation Outdoor ...
Страница 29: ...Issue 01 06 2023 Page 26 Figure 33 EU Declaration of Conformity Outdoor ...
Страница 30: ...Issue 01 06 2023 Page 27 Figure 34 EU Declaration of Incorporation Indoor ...
Страница 31: ...Issue 01 06 2023 Page 28 Figure 35 EU Declaration of Incorporation Outdoor ...