Issue: 01.06.2023
Page 26
FAULT
POSSIBLE CAUSE
CHECK
SOLUTION
Compressor starting too
frequently
Are controls set correctly - is the
differential on thermostat or LP
switch too small?
Check and adjust
Is the liquid line solenoid valve
allowing refrigerant to pass when
closed?
Check valve and clean seat or
replace as necessary if damaged
Discharge gas bleeding into
suction side
Does suction pressure rise
abnormally when compressor
stops or compressor fails to pump
down correctly?
Compressor valve reeds may be
damaged - replace compressor
CONDENSER FAN
Condenser fan will
not run
Power supply
See compressor will not start
section
See compressor will not start
section
Compressor contactor not
pulled in
See compressor will not start
section
See compressor will not start
section
Compressor contactor
pulled in
Is voltage being switched across
contactor?
If yes - check voltage to FSC and
to fan motor. If correct voltage
present at motor - fan faulty.
Replace fan
If no. Replace faulty contactor
Being controlled by FSC (if
fitted)
Is system operating pressure
below FSC setting?
If yes - all OK (check fan operates
when pressure rises)
Fan capacitor fault
Check visual condition of
capacitor and check capacitance
reading with capacitor meter.
Replace capacitor if required
Motor fault
If FSC fitted - bypass FSC to test
motor. If motor still does not run -
motor is faulty
Replace motor
Condenser fan
runs but only
slowly
Is fan being controlled by
FSC?
Is head pressure under control
(~14/15 bar on R448A/449A)
and fan speed increases as head
pressure rises?
All OK
Is head pressure above 16 bar
(R448/449A)?
Check setting of FSC. Adjust if
necessary.
FSC faulty
If fan runs slowly even after
adjusting FSC with head pressure
rising - FSC may be faulty
Change FSC
SYSTEM
Insufficient cooling
Lack of refrigerant
Is sight glass flashing continuously?
Leak test system and top up with
refrigerant
Condenser coil dirty
Visual check of coil condition
Clean condenser coil
Lack of ventilation to unit
Any obstructions around unit?
Clear same to ensure good
ventilation
Compressor not pumping
efficiently
Carry out pump test on
compressor
Replace compressor if fails pump
test
System settings
Controls (inc thermostat) set
correctly?
Adjust as necessary
T.E.V. Superheat
Adjust as necessary
Service valves do not open
correctly
Are valves fully open?
Adjust as necessary
Restriction in
piping/component
Is the filter drier blocked?
Sweating/frosting on outlet of
drier indicates a blockage
Replace filter drier
Damage to piping
Replace piping as required
Head pressure too
high
Condenser coil dirty
Visual check of coil condition
Clean condenser coil
System overcharged with
refrigerant
Is head pressure high but liquid
line cool to touch?
Reclaim refrigerant/recharge
correctly
Condenser fan not running
See above (fan will not run)
See above
FSC (if fitted) not set
correctly
Check setting against gauge
pressure
Adjust as necessary
Lack of ventilation to unit
Any obstructions around unit?
Clear same to ensure good
ventilation
System load too high
(overstocked, door open on
cold-room)
Reduce loading
Содержание V3 FUSION
Страница 30: ...Issue 01 06 2023 Page 27 Figure 33 Declaration of conformity Continued...
Страница 31: ...Issue 01 06 2023 Page 28...
Страница 32: ...Issue 01 06 2023 Page 29 Figure 34 Declaration of incorporation...
Страница 33: ...Issue 01 06 2023 Page 30 Figure 35 EU Declaration of conformity Continued...
Страница 34: ...Issue 01 06 2023 Page 31...
Страница 35: ...Issue 01 06 2023 Page 32 Figure 36 EU Declaration of incorpolation...