whereas a suction superheat that is too high will not 
provide enough cooling effect for the compressor and 
will cause high discharge temperatures. In either case, 
it is likely that compressor damage/failure will occur. 

 

 
Precautions when operate with FH and AJ 
Compressor 

 

Follow instructions below when operating

 

R448A/R449A in 

low temperature condensing unit which integrated with 
Tecumseh compressor FH/AJ. 
 

Limit the suction superheat below 10K, to 
ensure discharge temperature is maintained 
below 120ºC with evaporating temperature 
of -30ºC and below. Do not use capillary 

tubes as throttling devices to prevent plugging issue. 

 
 
 

Voltage Monitoring Device MG73BF 

(Applicable to JEHS-1400-B4-L-3 EVI; JEHS-1300-B4-M-3 
and JEHS-1500-B6-M-3 units only) 

 

Only the above models are equipped with voltage 
monitoring device to monitor the input power supply to 
protect the 3-phase compressor from overheating as result 
of working under phase lost, undervoltage or overvoltage.  
 

Table 8: LED indication on front plate of MG73BF  

                  LED  
 
(ON/OFF)   
Condition              

ON 

UV 

OV 

BLINK: 
ASY, ON: 
REV 

Power ON 

ON 

OFF 

OFF  OFF 

Phase reverse 

ON 

OFF 

OFF  ON 

Asymmetry 

ON 

OFF 

OFF  BLINK 

Under voltage 

ON 

ON 

OFF  OFF 

Over voltage 

ON 

OFF 

ON  OFF 

Phase Fail 

BLINK  OFF 

OFF  OFF 

Phase Fail when 
input voltages lower 
than UV set point 
and below 
asymmetry 

BLINK  ON 

OFF  BLINK 

Neutral Fail 

ON 

BLINK 

BLI
NK 

BLINK 

 
The off-delay timer will turn the system off after a set 
amount of time for following situation:

  

 

 

Supply phases exceed over 
voltage or under voltage trip 
level setting 

 

Any supply phase failure 

 

Line interruption 

 

Phase reverse occurrence 

 

Neutral failure 

 
 
 
 
 
 
 
 

Vapor Injection Controller EXD-HP1  

(Applicable to EVI units only) 

 

The controller EXD-HP1 used in the EVI units operates as an 

economizer control

. The setting of the controller is factory 

pre-set  and  is  password  protected.  Users  are  not 
recommended to change any settings in the controller.  

 

Electronic expansion valves in the EVI unit 
are in partially open condition. Do not 
charge the system with refrigerant before 
closure of valve.  
 

Four main parameters Password (H5), type of function 
(1uE), refrigerant type (1u0) and pressure sensor type (1uP) 
can be set only when digital input DI1 is off  
(open) while the power supply is ON (24Vac).  
 

Digital input Di1 

 

The digital status is dependent on the operation of 

system’s compressor or demand.

 

 

Table 9: Digital input status of EXD-HP1

 

Operating Condition 

Di1 status 

Compressor starts 

Closed (Start) 

Compressor stops 

Open (Stop) 

 
Electrical checked/modified before start-up 

 

To fully close the EEV, open circuit Di1-gnd of controller 
through disconnecting the supply to compressor. For  
1.

 

Model  JEHS-0951/1150-B4:  remove  the  jumper 
wire from terminal block labeled 8 and 9. 

2.

 

Model  JEHS-1300-B5:  remove  twin  jumper  bars 
from terminal blocks labelled 6 and 7.  

 

Switch ON the motor rated circuit to turn ON the power 
supply  24V  to  the  controller  EXD-HP1.  The  valve  will 
be driven to a close position.  

 

After  closure  of  the  EEV  valve,  start  charging  the 
system with refrigerant.  

 

Disconnect  power  supply  through  motor  rated  circuit 
breaker,  then  reconnect  back  the  original  wiring  from 
factory. 

 

 

Do  not  apply  voltage  to  the  system  before  all  cable 
connections are completed. 

 

Use a class II category transformer for 24 Vac power 
supply. Do not ground the 24 Vac lines.  

 

Higher  voltage  than  specified  will  permanently 
damage the controller. 

 

When  connecting  wires  of  EEV  and  pressure  sensor 
4~20mA  to  the  controller  EXD-HP1,  follow  the  cable 
color  to  connect  to  the  respective  abbreviation  color 
code printed on the EXD-HP1. Example for EXV: BR = 
Brown;  BL  =  Blue  etc.  Or  refer  to  wiring  diagram  for 
electrical connections. 

 

Содержание V3 FUSION

Страница 1: ...COMMERCIAL CONDENSING UNITS TECHNICAL MANUAL V3 FUSION FUSION SCROLL Commercial Condensing Units Medium Low Temperature Applications ISSUE 01 06 2023 V3...

Страница 2: ...to perform their assigned tasks properly and safely It is essential that prior to performing any task on this equipment this individual shall have read and understood this document and any referenced...

Страница 3: ...ECTION CONTROLLER EXD HP1 10 Table 9 Digital input status of EXD HP1 10 Figure 10 Display keypad unit LEDs and button functions 11 Table 10 Display parameters 11 Table 11 Parameter list for manual mod...

Страница 4: ...icator Oil Type A Uniqema Emkarate RL32CF Oil Type B Polyolester Oil Copeland Ultra 22 CC Copeland Ultra 32 CC Copeland Ultra 32 3MAF Mobil EAL Arctic 22CC Uniqema Emkarate RL32CF COP SEPR according t...

Страница 5: ...4 2 74 0 1 0 9 6 89 7 6 4100 1 2 1 1 8 125 40 JEHS 0680 B3 M 3 n a 2 96 n a 2 96 2 96 n c ZB48KQE TFD 18 80 1 80 11 4 19 1 101 0 1 0 9 6 89 7 6 4100 1 2 1 1 8 126 40 JEHS 0800 B4 M 3 3 10 3 12 2 95 2...

Страница 6: ...nd maximum working pressure are all suitable for the proposed application Check there is no damage to the units Any damage should be reported to the supplier immediately Check that the proposed equipm...

Страница 7: ...Figure 1 Positioning of condensing unit Ensure that there is no obstruction to air flow into or out of the unit Remove obstacles which block air intake or discharge Figure 2 Air circulation for conde...

Страница 8: ...f the system Tests must be conducted to ensure the amount of off cycle migration to the compressor does not exceed the compressor s charge limit Wherever possible the system should be installed to uti...

Страница 9: ...evacuation procedure is recommended for all new systems or where moisture is suspected Once the system is isolated and the vacuum pump is switched off any rise in pressure indicates that either there...

Страница 10: ...h sides of system Running the unit Run the unit and check compressor and condenser fan operation Check system pressures and temperatures gas charge and running currents of motors to ensure correct ope...

Страница 11: ...to stop the compressor should the discharge pressure exceed the compressor s high side operating pressure The high pressure switch can be set to lower values depending on the application and ambient c...

Страница 12: ...ll three phases at contactor in case of overtemperature For other 3phase models it is recommended to install the discharge thermostat with cut out temperature not more than the maximum discharge gas t...

Страница 13: ...in the EVI units operates as an economizer control The setting of the controller is factory pre set and is password protected Users are not recommended to change any settings in the controller Electro...

Страница 14: ...All alarms are disabled during manual operation We do not recommend unattended operation of the system during manual control Press and together for 5seconds to access to manual mode operation After a...

Страница 15: ...06 2023 Page 12 Outline Drawing Figure 11 Outline Drawing Series 1 Figure 12 Outline Drawing Series 2 Figure 13 Outline Drawing Series 3 Figure 14 Outline Drawing Series 4 Figure 15 Outline Drawing S...

Страница 16: ...2 N2 N1 ALM BLK F1U 3 15A MAX 50VA GRN YLW GRY M1F GRN YLW 1 M C2 WHT PPL RED BRN 3 BRN BLU BRN BRN NOTE 1 L N I I 2 B1 1 BRN I 4 6 3 5 BLU BLU 1 P LP 1 P 4 HP 3 S1PH S1PL RED 2 N2 N1 ALM BLK F1U 3 15...

Страница 17: ...D BLU M1C C R M 1 BLK GRN YLW Q1M S K1R 2 5 1 C2 C1 4 BRN BLK BLU BLU BLK BRN M1F GRN YLW 1 M C3 WHT PPL RED M1F E1HC 21 22 GRN YLW GRN YLW ORG N1 GRN YLW 1 M N3 BLK C3 1 ORG A2 N2 K1M BLU A1 1 LP BLK...

Страница 18: ...R C2 RUN CAPACITOR C3 FAN CAPACITOR E1HC CRANKCASE HEATER F1U FUSE K1M CONTACTOR K1R START RELAY M1C COMPRESSOR M1F CONDENSER FAN S1PH HIGH PRESSURE SWITCH S1PL LOW PRESSURE SWITCH 380 415V 3N 50Hz L2...

Страница 19: ...1C COMPRESSOR M1F CONDENSER FAN S1PH HIGH PRESSURE SWITCH S1PL LOW PRESSURE SWITCH NOTE 1 LPP 4 P HP 1 3 PE 21 22 GRN YLW GRN YLW BLK N2 GRN YLW 1 BRN M N3 BLU BLK C2 1 BLK A2 BLU N1 BLU BLU A1 3 BLK...

Страница 20: ...CONTROLLER B1 MOTOR CIRCUIT BREAKER C1 FAN CAPACITOR E1HC CRANKCASE HEATER F1U FUSE K1M CONTACTOR M1C COMPRESSOR M1F CONDENSER FAN S1PH HIGH PRESSURE SWITCH S1PL LOW PRESSURE SWITCH E1HC 22 21 BLK N3...

Страница 21: ...DICATOR FIELD WIRING A1P FAN SPEED CONTROLLER B1 MOTOR CIRCUIT BREAKER C1 FAN CAPACITOR E1HC CRANKCASE HEATER F1U FUSE K1M CONTACTOR M1C COMPRESSOR M1F CONDENSER FAN S1PH HIGH PRESSURE SWITCH S1PL LOW...

Страница 22: ...ONTACTOR M1C COMPRESSOR M1F M2F CONDENSER FAN S1PH HIGH PRESSURE SWITCH S1PL LOW PRESSURE SWITCH Q1R DISCHARGE THERMOSTAT 128 96 C Q1RP PHASE PROTECTOR MODEL B1 SETTING A JEHS 1300 B4 M 3 29 0 JEHS 15...

Страница 23: ...PE P P 13 14 Y1S Y1E M A2P 1 2 3 4 5 6 7 8 9 S1NPL R1T R2T t K1R 8 12 K1R 5 9 BRN BLK ORG YLW WHT 11 BRN BRN t BLU BRN PE L2 L1 I B1 4 2 6 I 1 3 I 5 BLK BRN GRY M 3 M1C K1M BRN 2 4 6 1 3 5 E1HC 22 21...

Страница 24: ...BLU BLU BRN BLK F1U 3 15A 2 3 4 BRN BLU BRN 240Vac 24Vac BLU GRN YLW GRY MAX 50 VA ALM 380 415V 3N 50Hz MODEL B1 SETTING A JEHS 1400 B4 L 3 EVI 25 0 S1PH S1PL B C A D PE P P GRN YLW N3 GRY GRY GRN YL...

Страница 25: ...the specific design and installation of your coil it may be beneficial to blow or vacuum out the rinse water from your unit to speed drying and prevent pooling 4 Compact Brazed Heat Exchanger BPHE For...

Страница 26: ...0500 B3 L 3 JEHS 0600 B3 L 3 JEHS 0750 B4 L 3 1 1 4 12UNF 110 135 Nm M38 1 5mm 42 47Nm JEHS 0951 B4 L 3 EVI 1 14 UNS 70 80 Nm M33 1 5mm 42 47Nm JEHS 1150 B4 L 3 EVI JEHS 1400 B4 L 3 EVI 1 3 4 12UNF 13...

Страница 27: ...ears if a fixed leak detection system is fitted e g 36 to 360 kg R448A At least once every 6 months 50 to 500 At least once every year if a fixed leak detection system is fitted 2 1000 A refrigerant c...

Страница 28: ...efrigerant levels Is there too little refrigerant in the system causing rapid LP tripping or too much refrigerant in the system causing HP tripping Check refrigerant level and adjust accordingly Fault...

Страница 29: ...by FSC Is head pressure under control 14 15 bar on R448A 449A and fan speed increases as head pressure rises All OK Is head pressure above 16 bar R448 449A Check setting of FSC Adjust if necessary FSC...

Страница 30: ...Issue 01 06 2023 Page 27 Figure 33 Declaration of conformity Continued...

Страница 31: ...Issue 01 06 2023 Page 28...

Страница 32: ...Issue 01 06 2023 Page 29 Figure 34 Declaration of incorporation...

Страница 33: ...Issue 01 06 2023 Page 30 Figure 35 EU Declaration of conformity Continued...

Страница 34: ...Issue 01 06 2023 Page 31...

Страница 35: ...Issue 01 06 2023 Page 32 Figure 36 EU Declaration of incorpolation...

Страница 36: ...Issue 01 06 2023 RJ0110030007408 J E Hall Limited Hansard Gate West Meadows Derby DE21 6JN England Tel 44 0 1332 253400 Fax 44 0 1332 371061 Email helpline jehall co uk www jehall com...

Отзывы: