JP5530 1-3KVA
5
diagram
:
1-3K input connection 1-3K output connection
2) UPS Output cable connection
1K(S)
、
2K(S)
、
3K(S) UPS can use output sockets
,
place the load socket into UPS output
sockets. Total output power shall not exceed 1KVA/1KW
、
2KVA/2KW
、
3KVA/3KW (0.8
output P.F can be optional), complete connection is shown as below
:
Apart from using the socket for output, 3K has the terminal block available for output as well
when the output current over 10A recommended. The wiring configuration is indicated as
below:
1) Remove the cover of the terminal block.
2) Use AWG14 or 2.1mm
2
wires for wiring configuration.
3) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
4) Put back the terminal block cover to the rear panel.
3.3.2 Operation procedure of external for long back up time UPS
The battery connection procedure is very important. Any incompliance may result in the risk
of electric shock. Therefore, the following steps must be strictly complied with
:
1) First connect the batteries of the pack in series, to ensure proper battery voltage
that ,1KL-36VDC,2KL-72VDC, 3KL-96VDC.
2) Take out the battery cable delivered with the UPS, one end of the external battery cable is
a plug for connecting the UPS, and the other end has 3 open wires for connecting the
battery pack.
3) Connect the external battery cable to the battery terminal (Don’t connect the battery
socket of the UPS first. Otherwise, it may cause electric shock).Connect the red wire to