Installation

CAUTION 

 Control the strength of the bolts before installation.

Hang the rubber anti-vibration pad to the bolt and balance the unit so that it remain horizontally. 

Make sure the unit is attached securely with a lock nut.

Anti-vibration pad

(vibration absorber)

Bolt (M10 or M12)

Lock nut

Nut

Washer

The distribution ducts should be connected to the unit through rigid or semi flexible ducts 

in order to avoid abnormal sounds and vibration. Flexible ducts may also be used ensuring 

that the structure of the duct does not block the air stream and cause vibration. The unit is 

equipped with pre-drilled duct flanges made of ABS for distribution duct connections.

Set the supplied ABS-made duct adapter to each duct connection to assure a good junction

 of the ducts.

Fit the ducts securely into the duct connection flanges and wind Aluminum tape

 to prevent

 air leakages.

Suspend the ducts from the ceiling so that their weight will not be applied to the unit.

The outdoor ducts must be covered with heat insulating material in order to prevent forming

of condensation.

CAUTION 

 Do not install the ducts as shown on the following figures. Doing so will increase the pressure

drop, decrease the air volume from the unit and give rise to abnormal sounds.

Extremely

sharp bends

Multiple

Bends

Bends right next

to the outlet. 

Sudden contraction and/or 

expansions in duct diameter

CAUTION 

 Before connecting the ducts, check that no sawdust or any other foreign material (scaps of

 

paper, vinyl, building material etc.) exist in the ducts.

 Make sure service doors open easily and fan/ filter can be pulled out.

 Pay attention to the warnings before connecting the units to ducts.

6

Preparation of roof bolts

Содержание JRH73 Series

Страница 1: ...JAKKA heat recovery units JRH73 Series User s Manual...

Страница 2: ...Contents Safety 1 Control List 2 Components 3 Dimensions 3 Installation 4 Maintenance 7 Technical specification 3 Troubleshooting 10...

Страница 3: ...he fresh outside air by a duct heater etc Select a position for introducing the outside air where no exhaust or combustion gases will be sucked into the fresh air duct and where it will not be covered...

Страница 4: ...re the drain hose is connected and check for any blockages through the drain line If needed clean it 06 Please check that the duct dimensions used in the duct system are correct and of the same dimens...

Страница 5: ...Power W 2x135 2x219 2x278 2x656 2x540 2x560 2x650 2x920 Maximum Current A 2x0 60 2x0 90 2x1 20 2x1 45 2x2 30 2x2 40 2x2 70 2x1 90 1 It is measured when external static pressure is 0 Pa 2 Sound level...

Страница 6: ...ut referring to the Installation and Operational Manual Check that the ground wire is securely connected Connect a fuse of specified capacity Do not install the unit remote controller and cable within...

Страница 7: ...t are made of ABS material hence do not need additional insulation After connecting the unit make sure that there is no leakage between the duct connections of the unit and the duct Use a duct tape wh...

Страница 8: ...Air Alternative Air Outlet Alternative Air Outlet Air Inlet Return Air or Outside Air Air Outlet Exhaust Air or Fresh Air Air Inlet Return Air or Outside Air Air Outlet Exhaust Air or Fresh Air Alter...

Страница 9: ...d junction of the ducts 2 Fit the ducts securely into the duct connection flanges and wind Aluminum tape to prevent air leakages 3 Suspend the ducts from the ceiling so that their weight will not be a...

Страница 10: ...Follow proper lockout tagout procedures to ensure the equipment cannot be inadvertently energized Secure drive sheaves to ensure rotor cannot freewheel Failure to secure drive sheaves or disconnect p...

Страница 11: ...factory set timer Remote controller informs the user to check the filters After the filters are cleaned by the user filter warning alarm must be reset NOTE It may be handy to keep spare clean and dry...

Страница 12: ...owder if need be Leave it to dry after cleaning and mount it to the unit after it is completely dry Tighten the service cover screws thoroughly and make sure the heat recovery exchanger does not fall...

Страница 13: ...Filters clogged or dirty a Change or clean filters b Air duct is clogged b Check the air ducts c Channel connections are incomplete c Check the duct system for leaks and complete the connections HIGH...

Страница 14: ...For Troubleshouting Please Contact Boulevard Zoran Djindjic 80 11070 Novi Beograd Tel 381 11 2600 901 Fax 381 11 2600 906 www jakkagroup com jakkagroup jakkagroup com...