Installation
JR(H/V)(B)70
www.jakkagroup.com
6
Ø 23
95
185
CONDENSATE DRAINAGE INSTALLATION (SIPH)
INSTALLATION OF WATER COIL AND ELECTRIC HEATERS
It's possible to install the optional PRE or POST heating devices such as water coils or
electric heaters (in the only possibile position, as showed in the picture)
These accessories are equipped with male/female spigots for the ducting connection and can
be installed on delivery and/or suction mouths of the units (direct installation) or in the circuit
of ducts (remote installation).
INSTALLATION OF THE WEATHER PROTECTION COWL
The weather protection cowl SKMF-R is recommended to protect ejection and suction mouths in case of installation outside the units ( birds, rain, etc.).
BA-AC
RCF
Electrical heater
| WRONG INSTALLATION
Electrical heater
RIGHT INSTALLATION
ONLY POSSIBLE POSITION
The unit is equipped with condensate drainage to evacuate the water during
normal operation.
Should always be provided with a drain pipe siphon and minimum slope of
3% in order to avoid stationing of condensate.
The siphon is essential for the proper functioning of the machine in order to
10,5
avoid sucking air and allow the natural flow of condensate