![Jaga DBH SET Скачать руководство пользователя страница 94](http://html.mh-extra.com/html/jaga/dbh-set/dbh-set_manual_631174094.webp)
94
B1.2. OPTION : THERMO-ELECTRICAL MOTOR
–
Valve opens in heating and cooling mode as soon as there is a control signal > 1V.
–
Valve closed in off mode & when the control signal is 0V.
MODE
MODE
MODE
Off
MODE
MODE
MODE
Speed 1
Speed 2
Speed 3
1
GND
0...10V
MODE
Option:
Thermo-electrical motor
Control
B 2. 0 - 10V BMS WITH WATER TEMPERATURE MONITORING
Configuration code : DPC.HC6120 / DPC.HC6220 / DPC.HC6423 / DPC.HC6523
[6]
ONLY DPC.HC6423 /
DPC.HC6523
B2.1. FACTORY SETTINGS
B2.1.1. Without control panel
- DPC.HC6120 / DPC.HC6220
The device is controlled via home automation. The unit starts as soon as there is a 0-10V control
signal and the set water temperature has been reached.
The unit starts as soon as the water temperature is > 28°C and the control signal is 0-10V.