40
JAGA NV | BRIZA 12 - JDPC.002 | MANUEL | 05.07.2021 | V.08
24 V +
GND
1
2P
4P
0-10 V
B. 0-10V WITH WATER TEMPERATURE MONITORING
Configuration code : DPC.BR72
B.1. FACTORY SETTINGS
The device is controlled via BMS.
The unit starts when there is a 0-10V control signal and the preset
water temperature has been reached.
The unit starts if the water temperature is > 28°C/82 ̊F and the control signal is 0-10V.
The unit starts if the water temperature is < 18 ̊C/64 ̊F and the control signal is 0-10V.
...
Fan speed in function of the incoming control signal.
curve : Speed versus 0-10V control signal
Min
1
0
10
BMS (V)
Max
[7]