EN
45
JAGA NV | BRIZA 12 - JFCC | MANUEL | 2023.03.06 | V.5.2
B.1. FACTORY SETTINGS
The device is controlled via auto-change-over. The unit starts when the preset water temperature is
reached. The user can temporarily select another mode manually.
Auto-change-over. The unit starts at the last selected speed(1, 2 or 3), if the water temperature > 28 ̊C.
Only with configuration code FCC.BRC62 / FCC.BRC64!
Auto-change-over. The unit starts at the last selected speed(1, 2 or 3), if the water temperature < 18 ̊C.
The unit is in standby. The unit automatically starts a new cycle if the preset temperature is reached.
Permanently off
All functions are disabled until the user switches on the unit via the control panel.
Fan speed is set according to the unit’s length.
B.2. CONTROL
Press and hold to switch modes (± 3 sec.)
When auto-change-over mode the controller itself will
select the desired operation mode. The user can always
choose manually a different mode of operation.
Manually changing the fan speed :
1
2
MODE
3
1
2
MODE
3
1
2
MODE
3
Fanspeed : 1
40%
Fanspeed : 2
60%
Fanspeed : 3
100%
Red LEDs are flashing: the water temperature for heating is too low
Blue LEDs are flashing: the water temperature for cooling is too high
3”
3”
3”
Only with configuration code
FCC.BRC62 / FCC.BRC64!
Window contact
The window contact is not activated by default and has to be activated /deactivated manually .
Switch on : turn on the DIP switch 1
1
2
3
4
5
6
7
8
ON
1
ON