Caution! It is prohibited to open this type of hydrant with a closed shutoff gate valve because the poppet
sliding down must be able to push a water column in the direction opposite to the flow direction during
the first phase of its movement.
2.2 MATERIALS DN80
List of basic materials used for the construction of an overground hydrant TYPE 8003 DN80 —
See table
Item Part name
Material
Reference standard
1
Main body
Cast-iron, EN-GJS 400-15
EN-GJS500-7
PN-EN1563: 2012
2
Ball chamber
Cast-iron, EN-GJS 400-15
EN-GJS500-7
PN-EN1563: 2012
3
Column
Cast-iron, EN-GJS 400-15
EN-GJS500-7
Steel 1.0254
Stainless steel 1.4301
PN-EN1563: 2012
PN-EN 1,503-3:2003
PN-EN 10088-1:2014
4
Seat
Brass
PN-EN 1982:2010
5
Poppet
Cast-iron, EN-GJS 400-15
EN-GJS500-7
EPDM
PN-EN1563:2012
PN-ISO1629:2005
6
Cap
Cast-iron, EN-GJS 400-15
EN-GJS500-7
PN-EN1563: 2012
7
Stem
Stainless steel 1.4021
PN-EN 10088-1: 2014
8
Spindle
Stainless steel 1.4301
PN-EN 10088-1:2014
9
Saddle tee
Aluminium, AlSi
PN-EN 1706:2011
10
Coupling
Cast-iron, EN-GJS 400-15
EN-GJS500-7
PN-EN1563: 2012
11
Lower body
Cast-iron, EN-GJS 400-15
EN-GJS500-7
PN-EN1563: 2012
12
Lower flange
Cast-iron, EN-GJS 400-15
EN-GJS500-7
PN-EN1563: 2012
13
Stopper
Brass
PN-EN 1982:2010
14
Stem nut
Brass
PN-EN 1982:2010
15
O-ring
EPDM
PN-ISO 1629:2005
16
Bolt
Stainless steel, A2
PN-EN ISO 4017: 2011
PN-EN ISO 4762: 2006
17
Nut
Stainless steel, A4
PN-EN ISO 4032: 2013
18
Ball
Cellular polypropylene or aluminium
alloy AlSi/EPDM
PN-EN 1706:2011
PN-ISO 1629:2005
19
Drainage
Polypropylene PP
PN-EN ISO 1873-1:2000