Electrical safety

Jacuzzi

®

hydromassage products are safe appliances, manu-

factured in compliance with 

EN 60335.2.60

EN 61000 

and

EN 55014

standards and approved by the 

Institute of Certi-

fication SIQ (Certifying Institute)

.

These are tested during production to guarantee user safety. 
Installation must be carried out by qualified and authorized per-
sonnel, in compliance with current national provisions.

It is the responsibility of the installer to select ma-
terials, to carry out work correctly, to check the con-
dition of the system that the unit is to be connect-
ed to so that it ensures user safety.  

Jacuzzi

® 

whirlpool baths are Class “I” appliances, and must be an-

chored securely and permanently connected to the electric mains
and earth system without any intermediate connections. 

The electric system and earth system of the build-
ing must be in working order and must comply with
the legal provisions and specific current regula-
tions in that country.

Means for disconnection of the appliance from the
supply after installation must be incorporated in
the fixed wiring in accordance with the wiring rules.

For connection to the mains, it is necessary to install a discon-
necting multiple-pole switch, and place it in an area that com-
plies with the safety prescriptions for bathrooms. 

The switch and other electrical devices must be lo-
cated, in compliance with regulations, in an area that
cannot be reached by the person using the appliance.

The installation of electrical devices and appliances (sockets,
switches, etc.) in bathrooms must comply with the legal re-
quirements and standards of the country concerned. In particu-
lar, no electrical installation is permitted within 60 cm of the tub
or at a height of less than 225 cm.

Connection to the electrical system of the building must be
made using a sheathed cable with characteristics not inferior to

H 05 VV-F 3x2,5 mm

2

.

The electric system of the building must be e-
quipped with a 0.03 A differential switch.

Parts incorporating electrical components, except
remote control devices, must be located or fixed
so that they cannot fall into the bath.

JACUZZI EUROPE S.p.A. shall not be held liable:

If installation is carried out by unqualified personnel and/or per-
sonnel unauthorized to carry out installation.

If the norms and legal provisions, regarding the electric sys-
tems of buildings, in force in the country in which installation
is carried out are not complied with.

If the instructions for installation and maintenance contained
in this manual are not followed.

If unsuitable and/or uncertified materials are used for instal-
lation.

If the tub is set up to function without conformity to the regu-
lations mentioned.

If incorrect operations are carried out that reduce the level of
protection against water jets or change the protection against
electric shocks by direct or indirect contact, or generate con-
ditions of abnormal insulation, current dispersion or over-
heating.

If any components or parts of the appliance are altered in re-
lation to the original state when supplied, releasing the Man-
ufacturer from any liability.

If the appliance is repaired by unauthorised personnel or if s-
pare parts are used other than the original ones supplied by
Jacuzzi Europe S.p.A.

Jacuzzi

® 

whirlpool tubs are equipped with a terminal,

fitted on the framework and marked with the sym-
bol 

, for equipotential connection of the surroun-

ding metal masses, as laid down by EN 60335.2.60
norms.

2

2

3

3

0

1

3

0

1

0,6 m

0,6 m

0,6 m

2,25 m

Содержание Projecta JP 7

Страница 1: ...ECTION PROJECT YOUNG COLLECTION by by JACUZZI vasche idromassaggio Schemi elettrici whirlpool baths Electrical diagrams baignoires d hydromassage Sch mas lectriques Hydromassagewannen Schaltpl ne ba e...

Страница 2: ...ca 3 Schemi elettrici 9 ENGLISH Electrical safety 4 Electrical diagrams 9 FRAN AIS S curit lectrique 5 Sch mas lectriques 9 DEUTSCH Elektrische Sicherheit 6 Schaltpl ne 9 ESPA OL Seguridad el ctrica 7...

Страница 3: ...alcuna installazione elettrica nella zona circostante la vasca per una distanza di 60 cm ed un altezza di 225 cm Per il collegamento all impianto elettrico dell immobile dovr es sere utilizzato un ca...

Страница 4: ...rical installation is permitted within 60 cm of the tub or at a height of less than 225 cm Connection to the electrical system of the building must be made using a sheathed cable with characteristics...

Страница 5: ...mes nationales en vigueur en particu lier aucune installation lectrique n est admise autour de la bai gnoire sur une distance de 60 cm et une hauteur de 225 cm Pour le branchement l installation lectr...

Страница 6: ...st zu beachten dass je de Art von Elektroinstallationen im Bereich der Wanne in einem Ab stand von 60 cm und in einer H he von 225 cm zu erfolgen hat F r den Anschluss an die elektrische Anlage des Ge...

Страница 7: ...se ad mite ninguna instalaci n el ctrica en la zona alrededor de la ba e ra a una distancia de al menos 60 cm y una altura de 225 cm Para la conexi n a la instalaci n el ctrica del edificio se debe ut...

Страница 8: ...8 Jacuzzi EN 60335 2 60 EN 61000 EN 55014 SIQ Jacuzzi I 60 225 05 VV F 3 2 5 2 0 03 JACUZZI EUROPE S p A Jacuzzi Europe S p A Jacuzzi EN 60335 2 60 2 2 3 3 0 1 3 0 1 0 6 m 0 6 m 0 6 m 2 25 m...

Страница 9: ...rra 1 4 L N ITALIANO display pump phase neutral earth ENGLISH display pompe phase neutre terre FRAN AIS display Pumpe Phase Nulleiter Erdleiter DEUTSCH display bomba fase neutro tierra ESPA OL JP 7 1...

Страница 10: ...neutral earth ENGLISH display contre fonction sec pompe capteur de niveau electrovanne phase neutre terre FRAN AIS display Trockenlaufschutz Pumpe niveausonde magnetventil Phase Nulleiter Erdleiter DE...

Страница 11: ...N N L 1 ON 0 OFF 1 ON 0 OFF display pompa fase neutro terra 1 4 L N ITALIANO display pump phase neutral earth ENGLISH display pompe phase neutre terre FRAN AIS display Pumpe Phase Nulleiter Erdleiter...

Страница 12: ...a a secco pompa fase neutro terra 1 2 4 L N ITALIANO display dry run device pump phase neutral earth ENGLISH display contre fonction sec pompe phase neutre terre FRAN AIS display Trockenlaufschutz Pum...

Страница 13: ...ra 1 2 4 5 6 L N ITALIANO display dry run device pump level probe solenoid valve phase neutral earth ENGLISH display contre fonction sec pompe capteur de niveau electrovanne phase neutre terre FRAN AI...

Страница 14: ...phase neutral earth ENGLISH display contre fonction sec blower g n rateur de bulles d air phase neutre terre FRAN AIS display Trockenlaufschutz Blower Luftblasenerzeuger Phase Nulleiter Erdleiter DEU...

Страница 15: ...ice phase neutral earth ENGLISH display contre fonction sec pompe variateur air phase neutre terre FRAN AIS display Trockenlaufschutz Pumpe Lufteintrittsregler Phase Nulleiter Erdleiter DEUTSCH displa...

Страница 16: ...al earth ENGLISH display contre fonction sec pompe capteur de niveau electrovanne variateur air phase neutre terre FRAN AIS display Trockenlaufschutz Pumpe niveausonde magnetventil Lufteintrittsregler...

Страница 17: ...earth ENGLISH display contre fonction sec pompe blower g n rateur de bulles d air variateur air phase neutre terre FRAN AIS display Trockenlaufschutz Pumpe Blower Luftblasenerzeuger Lufteintrittsregle...

Страница 18: ...splay contre fonction sec pompe capteur de niveau electrovanne blower g n rateur de bulles d air variateur air phase neutre terre FRAN AIS display Trockenlaufschutz Pumpe niveausonde magnetventil Blow...

Страница 19: ...pump phase neutral earth ENGLISH display contre fonction sec lectro aimant pompe phase neutre terre FRAN AIS display Trockenlaufschutz Elektromagnet Pumpe Phase Nulleiter Erdleiter DEUTSCH display mar...

Страница 20: ...earth ENGLISH display contre fonction sec lectro aimant pompe capteur de niveau electrovanne phase neutre terre FRAN AIS display Trockenlaufschutz Elektromagnet Pumpe niveausonde magnetventil Phase N...

Страница 21: ...SH display contre fonction sec lectro aimant pompe capteur de niveau electrovanne lampe phase neutre terre FRAN AIS display Trockenlaufschutz Elektromagnet Pumpe niveausonde magnetventil Strahler Phas...

Страница 22: ...tral earth ENGLISH display contre fonction sec lectro aimant pompes phase neutre terre FRAN AIS display Trockenlaufschutz Elektromagnet Pumpen Phase Nulleiter Erdleiter DEUTSCH display marcha atr s a...

Страница 23: ...GLISH display contre fonction sec lectro aimant pompes dispositif de chauffage phase neutre terre FRAN AIS display Trockenlaufschutz Elektromagnet Pumpen Heizger t Phase Nulleiter Erdleiter DEUTSCH di...

Страница 24: ...arth ENGLISH display contre fonction sec lectro aimant pompes capteur de niveau electrovanne phase neutre terre FRAN AIS display Trockenlaufschutz Elektromagnet Pumpen niveausonde magnetventil Phase N...

Страница 25: ...fonction sec lectro aimant pompes capteur de niveau electrovanne lampe dispositif de chauffage phase neutre terre FRAN AIS display Trockenlaufschutz Elektromagnet Pumpen niveausonde magnetventil Strah...

Страница 26: ...contre fonction sec lectro aimant pompes capteur de niveau electrovanne b ite de lampe dispositif de chauffage phase neutre terre FRAN AIS display Trockenlaufschutz Elektromagnet Pumpen niveausonde m...

Страница 27: ...eur distributeur lectrovanne d sinfection d viateur 3 voies protection thermique du moteur interr niveau r servoir d s motor ducteur d viateur 3 voies display alimentation inverter commande inverter i...

Страница 28: ...anne d sinfection d viateur 3 voies protection thermique du moteur interr niveau r servoir d s motor ducteur d viateur 3 voies Cromodream display alimentation inverter commande inverter inverter pompe...

Страница 29: ...nti interference filter barrette de connexion alimention pompe 3 alimentation spots base recharge batterie de t l commande plaque bord baignoire contre fonctionnement sec commande spots Cromodream ele...

Страница 30: ...inverter power supply inverter control inverter dry run device phase neutral earth pompe r cepteur lectrovanne d sinfection interr niveau r servoir d s protection thermique du moteur lampe dispositif...

Страница 31: ...infection tank level switch air variation device spotlight heater electromagnet dry run device phase neutral earth pompe r cepteur lectrovanne d sinfection interr niveau r servoir d s variateur air la...

Страница 32: ...jacuzzi eu spagna jacuzzi it I dati e le caratteristiche non impegnano la Jacuzzi Europe S p A che si riserva il diritto di apportare tutte le modifiche ritenute opportune senza obbligo di preavviso...

Отзывы: