7.0 Electrical Wiring Instructions
IMPORTANT NOTICE:
The electrical wiring of this spa must meet
the requirements of the National Electrical Code/USA (NEC) and any
applicable state or local codes. The electrical circuit must be installed
by a qualified electrician and approved by a local building/electrical
inspection authority.
.
Convertible 120/240V Power Models:
•
120V “Plug-in” Operation:
This spa must operate on the supplied
20V GFCI cord at its original length or must be hard-wired for
longer runs.
NEVER USE AN ExTENSION CORD FOR ANY REA-
SON!
•
Convertible 120/240V Operation:
The included 20V GFCI cord
must be discarded for 240V operation. This spa must be hard wired.
Supplying power to either configuration above which is not in accor-
Export J-210 / J-220 1-Pump Models (50Hz)
230V/20A*
230V/30A**
Voltage:
230 VAC
230 VAC
# of Wires:
3
3
Frequency:
50Hz
50Hz
Current Draw:
5A
2A
Circuit Breaker:
20A
30A
*
In the 20A configuration, the heater
will not operate
while the jets
pump is running in high speed.
This is the factory setting.
**
In the 30A configuration, the heater
will operate
while the jets pump
is running in high speed.
Export J-230 2-Pump Model (50Hz)
230V/20A*
230V/30A**
230V/40A***
Voltage:
230 VAC
230 VAC
240 VAC
# of Wires:
3
3
3
Frequency:
50Hz
50Hz
50Hz
Current Draw:
5A
23A
29A
Circuit Breaker:
20A
30A
40A
*
In 20A configuration, the heater
will not operate
while either jets
pump is running in high speed.
This is the factory setting. Note:
pump 2 runs only in high speed.
**
In the 30A configuration, the heater
will operate
while one jets
pump is running in high speed.
Note: pump 2 runs only in high
speed.
***
In 40A configuration, the heater
will operate
while both jet pumps
are running in high speed.
Note: pump 2 runs only in high speed.