Quick Installation and Startup Guide
Insert a small coin
(dime) in the release
slot located on the
bottom of the
thermostat and gently
twist the coin to
release the thermostat
from the subbase.
Before mounting
the thermostat
subbase to the
wall, pull the
wires from the
HVAC unit
through the wire
access hole.
Mount and level
the subbase
using the
furnished
hardware.
After all wiring is landed, attached the thermostat to the subbase and apply 24 Volt power.
Land the remaining HVAC wires to the thermostat terminals based on the specific equipment configuration. If an indoor or outdoor remote sensor is used, wire the sensor to the T T terminals.
The sensor wiring must be a separate 18-2 cable and should not exceed 200’ in length from the sensor to the thermostat.
Refer to the thermostat Installation Manual for Advanced Installer settings that might be
required for the specific equipment applications as well as confirming that the baud rate is
set at 19.2 and the Modbus address is set at 01.
To simplify installation,
the transceiver comes
pre-wired to the
thermostat terminals with
leads for the HVAC unit
24 Volt hot and common.
Use wire connectors to
secure each lead to the
HVAC unit 24V ‘R’ and
24V ‘C’ wires. Land the
remaining HVAC unit
wires to their proper
terminals. Dress all wires
so that they do not come
in contact with the
thermostat PC board.
Set the system slide switches to match the
HVAC equipment application:
* For heat pump systems that energize the reversing valve on a call for heating (B), turn switch 4 ON.
SWITCH 6 MUST BE OFF AND SWITCH 8 MUST BE ON
Use the provided
6 transceiver log
to document the
serial number
located below the
bar code on the
back of the
thermostat
subbase. Also
note the
thermostat
location.
Turn the two
Modbus
configuration
slide switches
to ON.
. . . . . .
1 2 3 4 5 6 7 8
ON
. . . . . .
1 2
ON
. . . . . .
1 2 3 4 5 6 7 8
ON
. . . . . .
1 2
ON
SLIDE SWITCH SETTING
HVAC SYSTEM
6=
1 HEAT / 1 COOL
8=
5=ON
4=OFF
3=OFF
2=OFF
1=OFF
7=OFF
2 HEAT / 2 COOL
6=
5=ON
3=ON
2=OFF
1=OFF
4=OFF
8=
7=OFF
6=
8=
1=OFF 2=ON 3=OFF 4=OFF 5=ON
7=OFF
2 HEAT / 1 COOL
HEAT PUMP (O)*
6=
8=
4=OFF 4=ON
3=ON
2=ON
1=OFF
7=OFF
OFF
ON
OFF
ON
3 HEAT / 2 COOL
HEAT PUMP (O)*
OFF
ON
OFF
ON
W2
G3
Y2
G2
W1
O/B
Y1
G1
R
B
A
24 24C
T
T
REV
VALVE
FAN 1
RELAY
TRANSCEIVER
THERMOSTAT OPTIONAL
SENSOR
LINE
COMP 1
AUX
RELAY
HEAT
24 V
W2
G3
Y2
G2
W1
O/B
Y1
G1
R
B
24C
24
A
T
T
REV
VALVE
FAN 1
RELAY
TRANSCEIVER
THERMOSTAT OPTIONAL
SENSOR
LINE
COMP 1
RELAY
COMP 2
AUX
RELAY
HEAT
24 V
W2
G3
Y2
G2
W1
O/B
Y1
G1
R
B
24 24C
A
T
T
HEAT 1
RELAY
FAN 1
RELAY
TRANSCEIVER
THERMOSTAT OPTIONAL
SENSOR
LINE
COMP 1
RELAY
COMP 2
RELAY
HEAT 2
RELAY
24 V
Multi-Stage Heat / Cool
Single Stage Heat / Cool
3 Heat / 2 Cool Heat Pump or Dual Fuel
2 Heat / 1 Cool Heat Pump or Dual Fuel
LAND HVAC
UNIT WIRES
TO APPROPRIATE
TERMINALS
W2 Y2 W1 Y1 G R
O/B
24 24C B A T T
C
R
The HVAC 24 Volt power must be OFF during wiring!
MN:1000140 R:100
SN: AU111400000
BACK OF SUBBASE
MOUNTING
TRANSCEIVER
(Push in on sides to release cover)
HOLES
FRONT OF SUBBASE
W2
G3
Y2
G2
W1
O/B
Y1
G1
R
B
24 24C
A
T
T
HEAT
RELAY
FAN 1
RELAY
TRANSCEIVER
THERMOSTAT OPTIONAL
SENSOR
LINE
COMP 1
RELAY
24 V