REMOTE SENSOR INSTALLATION
Locate the sensor in the same manner as the thermostat. Mount the sensor 18” away
from any outside wall. Do not install the sensor behind doors, in corners or other dead
air spaces. Keep the sensor away from direct air flow, supply registers or near sources
of heat such as lamps and appliances. The maximum wire length from the sensor to
the thermostat is 300 feet. Use a separate 18-2 shielded cable for sensor wiring. Prior to
wiring the sensor to the thermostat, use an ohm-meter or multi-meter to measure the
resistance of the sensor. Measure at the end of the wires that will connect to the
thermostat. Confirm the resistance value (within 5%) to the temperature where the
sensor is mounted. Use a quality digital electronic thermometer to read the
temperature at the sensor. Remove the sensor cover and place the thermometer probe
next to the sensor element to verify an accurate reading. Disconnect power to the
thermostat when wiring the sensor, strip only as much insulation off of the wires as
necessary to provide a good contact with the terminals. The sensor is not polarity
specific so either sensor lead may be connected to the SC or S1 terminals on the
thermostat.