NB: When laying the sensor cable please ensure that no part of the cable comes into
contact with another part of the cable, and that no part of the sensor cable comes
into contact with metal surfaces, as this may trigger the alarm.
SMOKE DETECTOR
The relevant Alarm (1 or 2) should be configured as
‘
Normal Open
’
in the browser
via the EMD set-up screens [
Device Management/Device Configuration
].
When smoke is detected, an audible alarm will sound and the interSeptor Pro-XP will
be activated and the sensor
’
s alarm state will change from
‘
Normal
’
to
‘
Alarm
’
.
Please refer to the smoke detector manual for the correct physical installation of the
sensor.
SECURITY SENSOR
The relevant Alarm (1 or 2) should be configured in the browser via the EMD set-up
screens [
Device Management/Device Configuration
] to be
either “Normal Close”
or
‘
Normal Open
’
, depending on the security sensor
’
s deployment. When a security
incident is detected, the interSeptor Pro-XP will be activated and the sensor
’
s alarm
state will change from
‘
Normal
’
to
‘
Alarm
’
.
VOLTAGE SENSOR / PIR SENSOR / VIBRATION SENSOR
The relevant Alarm (1 or 2) should be configured as
‘
Normal Open
’
in the browser
via the EMD set-up screens [
Device Management/Device Configuration
].
When power is lost, movement detected or vibration sensed the status of the sensor
will change from
‘
Normal
’
to
‘
Alarm
’
.
NB: The Voltage Sensor LED does not indicate status and can therefore be ignored.
DRY CONTACT CABLE
The dry contact cable can be used to monitor any device with a normally
open/closed contact or high/low alarm output. Connect the dry contact cable to the
relevant equipment (fire panel, air conditioning unit, UPS, etc) according to the
manufacturer
’
s instructions. C
onfigure the correct alarm setting for a ‘
Normal Open
’
or
‘
Normal Closed
’
state (depending on the equipment/alarm being monitored) via
the EMD set-up screens [
Device Management/Device Configuration
] on the
interSeptor Pro-XP browser interface.
When an alarm event is detected, the status of the sensor will change from
‘
Normal
’
to
‘
Alarm
’
.
DISCLAIMER :
Please note that the interSeptor Pro-XP and its sensors are only intended for
monitoring environments and should only be used for that purpose. The
interSeptor Pro-XP and its sensors should NOT be used in safety-critical
applications or relied upon as human safety devices.