Once connected, the status of the Temperature/Humidity sensors can be viewed
on the
Device Monitoring/Comprehensive View
page of the web browser.
The Temperature/Humidity sensors can also be daisy-chained (with a maximum of
8 sensors per chain) by adjusting the dip switch settings on the bottom of each
sensor. Please refer to the table in
Appendix I
at the end of this guide.
M3x0.5 (length: 6~8mm) screws can be used to fix a DIN Rail Mounting Kit to the
rear of the interSeptor Pro-XP.
7.
Jacarta Go-Probe alarm sensors (Water Leak, Smoke, Power, Security, etc.) can
be connected to the dry contact ports on the Temperature/Humidity sensors via
the screw terminals (2 x Go-Probe sensors per T/H sensor).
8.
Sensor settings (to trigger alerts, etc.) can be configured via the
Device
Management/Device Configuration
menu options. Please follow the
instructions provided with each sensor. On the Web UI, Port 1= EMD 1, and so on.
9.
An optional Jacarta Alarm Siren/Beacon can be connected to the ports on the
interSeptor Pro-XP that are marked
DO
using the terminal block that is attached
to the end of the Alarm Beacon cable. The beacon/siren can be configured to
activate when there is an alarm by selecting
Event Output
for the relevant
Temperature/Humidity sensor(s) via the
Device Management/Device
Configuration
settings within the web browser UI.