The JA-151ST Wireless combined smoke and heat detector

The JA-151ST Wireless combined smoke and heat detector

1 / 2

MLW55806

The JA-151ST is a component of the 

JABLOTRON JA-100

alarm system. It is used to detect fire hazards in the interior of 
residential or commercial buildings. The detector can be installed in 
mobile homes or caravans. The product is not designed to be 
installed in industrial premises. The JA-151ST detector uses 
wireless communication and it is powered with three AA batteries. 
The detector should be installed by a trained technician with a valid 
with a valid manufacturer’s certificate.

The detector indicates a fire hazard using the built-in LED 

indicator and acoustic signalling. 

The JA-151ST consists of two independent detectors – an optical 

smoke detector and a heat detector. The optical smoke detector 
works on the principle detection of scattered light. It is very 
sensitive to large dust particles which are present in dense smoke. 
It is less sensitive to smaller particles generated by the combustion 
of liquids such as alcohol. That is why the fire detector also contains a 
built-in heat detector which has a slower reaction but is much better at 
detecting fire which generates only a small amount of smoke.

Detector range and location

The smoke detector must be installed so that any smoke easily 

drifts into the detector owing to natural thermal currents, e.g. on the
ceiling. It is suitable for residential buildings but not suitable for free 
spaces, outdoor environments or interiors with extremely high 
ceilings (above 5 m) where fire by-products can disperse over a 
large area – the smoke would not reach the detector position.

The detectors should be installed by a trained technician with a 

valid manufacturer’s certificate.

Detectors should be installed in the building according to the 

project documentation. If such documentation is not available, their 
position should comply with the effective standards for fire alarm 
signalling systems.

The detector must always be placed in the section leading to the 

exit of the building (escape route), see

Fig. 1

. If the building has a 

floor area greater than 150 m

2

, installation of an additional detector 

in some other suitable place is required, see 

Fig.2

.

Fig 1

Fig 2

Fig 3

1. kitchen, 
2. living room, 
3. – 6. bedrooms

y

/

basic coverage

{

/

recommended 

coverage

0,9 m

Fig 4

Fig 5

centre of the room, best location

acceptable location

In multi-storey flats and family houses the detector should be installed 

above the stairs. It is recommended to place additional detectors in 
rooms where people sleep. See 

Fig 3

.

Installation on level ceilings

Place the detector in the centre of the room if possible. 

The 

detector must not be recessed 

into the ceiling due to the possible 

existence of a cool air layer on the ceiling.

Never place the 

detector in the corner of the room 

(always keep at least 0.5 m 

distance from the corner - see Fig 4). There is an insufficient 
circulation of air in the corners.

Installation on sloping ceilings

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5. 

Walls, partitions, barriers and lattice ceilings

The 

JA-151ST 

detector must not be installed closer than 0.5 

m from any wall or partition. 

A narrow room with a width of less than 

1.2 m requires the detector(s) to be placed at a distance of at least one 
third of the room’s width away. In a case when a room is separated 
into sections with furniture, racks or semi partition walls which do 
not reach the ceiling, the space is considered to be fully separated 
if the gap between the top of these and the ceiling does not exceed 
0.3 m

.

A free space of at least 0.5 m is required under and around the 

detector. Any irregularities of the ceiling (e.g. girders) exceeding 5 % of 
the ceiling height should be considered a wall and the above mentioned 
limitations should apply.

Ventilation and air circulation

The detectors must not be installed directly by ventilation or air 

conditioning vents.

In the case of air being supplied through a 

perforated ceiling, each detector must be placed so that no 
perforation hole occurs within 0.6 m of the detector.

Avoid installing the detector in the following locations:

x

places with poor air circulation (niches, corners, apexes of A-
shaped roofs, etc.)

x

places exposed to dust, cigarette smoke or steam

x

places with over-intense air circulation (close to ventilators, 
heat sources, air conditioning outlets, etc.)

x

in kitchens and other cooking places (because steam, smoke or 
oily fumes can cause false alarms or reduce detector sensitivity).

x

beside fluorescent lights or energy-saving light bulbs (electrical 
interference can cause a false alarm)

x

in areas with lots of small insects

Warning:

Most false alarms are caused by improper detector 

location.

See CEN/TS 54-14 standard for detailed installation guidelines.

Installation

When installing the detector, abide by the procedures 

recommended in the previous paragraphs.

Fig 6: 1– detector cover opening; 2 – detector cover closing; 3 – optical 

status signalling; 4 – arrow showing where to insert the detector; 

5 – production code; 6 – configuration terminals; 7 – battery holders;

8 – button  for  test

1.

Open the detector cover

, by turning it anti-clockwise 

(1) 

2.

Attach the plastic base

to the selected place using screws 

3.

Use the terminals (6) to set the required detector function 

see the table below 

1

ON

Siren disabled

3

OFF

Smoke (EN 14604 or 
EN 54-7) or heat (EN 
54-5)

OFF

Siren enabled
(EN 14604)

4

OFF

2

ON

Memory disabled 

3

OFF

Smoke only (EN 14604 
or EN 54-7) (not heat)

OFF

Memory enabled
(EN 54-7 and EN 54-
5)

4

ON

ON

OFF

3

ON

Heat only (EN 54-5) 
(not smoke)

4

OFF

3

ON

Both smoke and heat 
(both conditions at the 
same time)

4

ON

When the detector is installed in caravan trailers, use only the 
“smoke only“ or “both smoke and heat” settings.