JA-151IR wireless 4beam optical barrier
JA-151IR wireless 4beam optical barrier
2 / 2
MMY51902
When the setting is complete, it is followed by adjustment of the receiver
unit:
Fig. 5 Setting up using a multimeter
A permanently lit LED on the transmitter/receiver indicates that the beam has
been interrupted (or wrongly adjusted). The better the beam reception, the
longer the break between the LED flashes – see fig. 8, LED 2. When the LED
stops flashing, continue looking for the ideal position indicated by the highest
voltage measured on the voltmeter (see fig. 5). The ideal measured value
should be
higher than 2.4 V
.
Setting up the electronic part of the barrier
Both units are equipped with settings switches. Each barrier has specific
beam modulation so that´s why several barriers can be installed near each
other. The barriers cannot influence each other.
There is a DIP switch on the receiving unit with six switches. It is possible
to set the beam modulation (the setting has to be the same on the receiver
as on its partner transmitter). For beam modulation setting see figure 6. For
examples of installations, see the original manual in the delivery pack. It is
possible to set a 2 minute sleep time after an alarm (beam interruption) in
order to save the batteries. The setting is done by switching switch no. 3 to
the ON position. The auxiliary output is set by DIP no. 4.
Don´t change
this
setting, it ensures the correct triggering of the fault status. DIP switches no. 5
and no. 6 determine the reaction sensitivity. See options for settings in fig. 7.
Note:
If the beam strength is reduced (less than 50%) for more than 20 s,
it triggers a fault and a report is sent to the control panel.
Fig. 6 beam modulation setting
Fig. 7 Reaction time setting
Testing
Perform the barrier test in three places (A, B and C – next to both the units
and in the centre). The setting is completed only if the barrier reacts
successfully in all three positions. You should also check the signal
transmission to the system control panel. Only then is it possible to put back
the unit covers and secure them and then perform the final test.
Fig. 8 Barrier function test
The indication LEDs on the units (fig. 8) have the following functions when
the tamper is unlocked:
Alarm (1)
indicator lights when the beam is interrupted.
Level indicator (2),
the better the beam reception, the longer the break
between the LED flashes.
Low Battery (3)
indicators flash if the batteries in the unit are discharged.
Always replace both (all) batteries at the same time. (SAFT LSH20 lithium
batteries).
Power (4)
indicator- lights when the transmitter unit works.
A
B
1
2
3
4
3
Fig. 9 Indication LEDs in units: A – Receiver,
B – Transmitter, 1 –
Alarm
, 2 – Beam quality
Level –indicator
,
3 –
Low Battery
indicator, 4 –Transmitter operation indication
(
Power
)
Replacing the batteries
The detector checks the battery status automatically and if the batteries
are running low, it informs the system. The detector remains fully functional.
The batteries should be replaced as soon as possible (within 1 week). Use
SAFT LSH20 lithium batteries
and always replace all at the same time. If it
is needed to increase the lifetime of the batteries you can add two more
batteries. Then you have 4 batteries in one unit.
Technical specifications
Power
4x (8x) LSH20 type lithium batteries (3.6 V / 13 Ah)
Average battery lifetime
approx. 3 years* (6 years)*
* with 120 s energy saving mode
Communication band
868.1 MHz, JA-100 protocol
RF range
up to 300 m (open area)
Optex barrier parameters
Distance between barrier units
max. 100 m
Barrier installation height
0.7 – 1.0 m
Object motion speed
as set by an installer
Enclosure protection
IP65
Max. relative humidity of the environment
95 %
Weight (re transmitter)
3300 g
Operational environment according to EN 50131-1
IV
Operational temperature range
-20 °C to +60 °C
Security grade
according to OPTEX
Complies with
ETSI EN 300220, EN 50130-4,
EN 55022, EN 60950-1
Can be operated according to
ERC REC 70-03
JABLOTRON ALARMS a.s. hereby declares that the JA-151IR module is in
compliance with the essential requirements and other relevant provisions of
Directive 1999/5/EC, 2011/65/EU. The original of the conformity assessment
can be found at
www.jablotron.com
- Technical Support section
Note:
Although this product does not contain any harmful materials we suggest
you return the product to the dealer or directly to the producer after use. For
more detailed information visit
www.jablotron.com
.
138
83
45
2
8
3,
5
2
22
3
90
2
65
Obr. 10 Dimensions of units