INDEX
All J4C actuators are supplied with a local visual position indicator comprises a black base with a
yellow insert that shows, both the position and direction of rotation (Fig.6).
The open and close positions have the following logos molded into the top cover OPEN 90 and
CLOSE 0. Opening = Closing =
Electrical connection: All models.
ON - OFF VAC
The power supply is connected to the grey “A” DIN plug (Fig.3).
Neutral PIN 1 + Phase PIN 2 = Close actuator
Neutral PIN 1 + Phase PIN 3= Open actuator
Earth/ground connection - Flat PIN on top.
The volt free connection (conf. of position) black “C” DIN plug (Fig.3)
Common PIN 1 + PIN 2 = Close confirmation of position
Common PIN 1 + PIN 3 = Open confirmation of position
POSITIONER VAC VDC
The power supply is connected to the grey “A” DIN plug (Fig.5).
Neutral/negative PIN 1 + Phase/positive PIN 2 - Power supply
Earth/ground connection - Flat PIN on top.
Input/output signal is connected to the black “B” DIN plug (Fig.5).
Negative PIN 1 + positive PIN 2 = Input signal
Negative PIN 1 + positive PIN 3 = Output signal
The volt free connection - black “C” DIN plug (Fig.5).
Common PIN 1 + PIN 2 = Close position confirmation
Common PIN 1 + PIN 3 = Open position confirmation
(Fig.5)
A
C
B
(Fig.3)
A
C
ON - OFF VDC
The power supply is connected to the grey “A” DIN plug (Fig.4).
Negative PIN 3 + Positive PIN 2= Close actuator
Negative PIN 2 + Positive PIN 3= Open actuator
Earth/ground connection - Flat PIN on top.
The volt free connection (conf. of position) black “C” DIN plug (Fig.4)
Common PIN 1 + PIN 2 = Close confirmation of position
(Fig.4)
A
C
3. LOCAL VISUAL POSITION INDICATOR
Fig. 6 0 = CLOSE
Fig. 6 90 = OPEN
03
INDEX
ENGLISH