![IXOM ResidualHQ Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/ixom/residualhq/residualhq_control-manual_2098828014.webp)
Base ► Configure ► Trending and Historical Data
Name
Name
Units
Units
Def.
Def.
Low
Low
High
High
Description
Description
Trending Data
Register Period
mins
1
0
32767
Minutes between logging of trending data values
Residual Trend
Points
5
0
32767
Number of data points averaged for “recent” data
Chlorine Vol. Limit
gals
12.0
000.0 330.0 Feed volume limit (24 hour period)
Ammonia Vol. Limit
gals
12.0
000.0 330.0 Feed volume limit (24 hour period)
Unaccounted
Change Limit
%
10.00 0.00
100.0 Unaccounted change monitor. If the bulk storage sensor reports an
unaccounted change (no dosing/reset for fill) in the set period the system
will report an error.
Unaccounted
Change Timeout
hrs
15
0
24
Unaccounted change monitor. If the bulk storage sensor reports a change
greater than the limit during this time period, the system report an error.
Low Level Chlorine
?
15
*
*
Low level alert for bulk chlorine storage. Units and Low/High limits
user-defined.
Low Level Ammonia
?
15
*
*
Low level alert for bulk chlorine storage. Units and Low/High limits
user-defined.
Low Level Monitor
Tank
?
15
*
*
Low level alert for monitored tank. Units and Low/High limits user-defined.
Tank Sensor Units
‘%’
User-defined String for Tank Sensor Units. Max of 4 characters.
Tank Sensor Min.
?
0.0
(-)
(+)
User-defined Floating point low limit for Tank Sensor. Used to scale input
value (linear).
Tank Sensor Max.
100.0 (-)
(+)
User-defined Floating point high limit for Tank Sensor. Used to scale input
value (linear).
Bulk Chlorine Units
‘%’
User-defined String for Bulk Chlorine Storage Units. Max of 4 characters.
Bulk Chlorine Min.
?
0.0
(-)
(+)
User-defined Floating point low limit for Bulk Chlorine Storage. Used to scale
input value (linear).
Bulk Chlorine Max.
100.0 (-)
(+)
User-defined Floating point high limit for Bulk Chlorine Storage. Used to scale
input value (linear).
Bulk Ammonia Units
‘%’
User-defined String for Bulk Ammonia Storage Units. Max of 4 characters.
Bulk Ammonia Min.
?
0.0
(-)
(+)
User-defined Floating point low limit for Bulk Ammonia Storage. Used to scale
input value (linear).
Bulk Ammonia Max.
100.0 (-)
(+)
User-defined Floating point high limit for Bulk Ammonia Storage. Used to
scale input value (linear).
©2022 IXOM Watercare Inc. | www.ixomwatercare.com | 866 - 437 - 8076 | [email protected]
Menu
Configuration
Configuration Menu
Parameter Information
10360_20220119
ControlManual_ResidualHQ_10380_20220809a - 12