56
Set the time up, fast and life alarm behaviour and push the ENTER keys.
Move between digits with the SELECT key and change numerical values with the UP and DOWN keys.
When setting the time up alarm, enter the maximum allowable time for a proximity switch to detect the
connecting plate.
Push the ENTER, RESET, SELECT, UP or DOWN key to return to the alarm setting sub-
menu or the MENU key to return to the main menu.
Setting confirmation (4. SETTING: 3. SET VALUE CONFIRMATION)
Setting details can be checked through "3. Set value confirmation".
■ Stroke length confirmation
The LPC-1 controller shows stroke length measured through teaching.
LEFT: Stroke length measured with the left displacement sensor.
RIGHT: Stroke length measured with the right displacement sensor.
AVE: Average stroke length of the measured stroke lengths.
■ Pump model
The LPC-1 controller shows the selected pump model code.
■ MANU or AUTO
The LPC-1 controller shows the current operation mode of MANU or AUTO.
■ Drive mode
The LPC-1 controller shows whether operation is with feedback control or not. "QUANT.CONST.CTL" repre-
sents operation with feedback control and "LOW PULSE MODE" represents no feedback control.
Select "3. SET VALUE CONFIRM" in the sub
menu and push the ENTER key.
4
5
1
Operation programming