4.4. - Circulation
Settings
4.4.1. - Circulation
Mode of circulation
When the mode
“Request”
is active, the circulation pump is switched on after a corresponding
tapping of water has occured and stays on until the circulation target temperature (Circ Tmin +
hysteresis) is reached at the circulation sensor.
In mode “
Periods
” the circulation pump is enabled in the set periods and the set circulation
minimum temperature is undershot and stays on until the circulation target temperature (Circ
Tmin + hysteresis) is reached at the circulation sensor.
Time
: The circulation pump is switched on in the enabled periods and the set circula-
tion minimum temperature is undershot, or when water is tapped. Circulation stays on till the
circulation target temperature (Circ Tmin + hysteresis) is reached at the circulatiopn sensor.
Always on
: Circulation pump is switched on in set periods.
4.4.2. - Circ. Tmin.
Minimum temperature at sensor S2
If the temperature drops below Circ.Tmin and the circulation is enabled (see „4.4.5. -
Circulation period“), the circulation pump is started.
4.4.3. - Circ. hysteresis
4.4.4. - Circ. maximum Flow rate
Switch-off hysteresis of the circulation pump
If the temperature exceeds TminS2 by this value, the circulation pump is switched off.
Maximum fl ow rate of the circulation pump
If the fl ow rate measured at sensor 6 exceeds this value (because water is being drai-
ned from the system) the circulation pump is switched off.
Circulation settings are only availabe when the circulation function was
selected for relay 1 in special functions.
Caution
This Value is set during the calibration process.
Caution