Page 45
Operation and Maintenance
Envistar Flex
DSEF191101.05.EN
Continuous product development may give rise to specification changes without notice.
Inspection
DANGER!
Risk of serious personal injury and/or damage to air handling
unit.
Read and understand the entire chapter "1.5 General safety
messages" before working on, servicing, or inspecting the air
handling unit.
1
2
1. Prepare access:
Size
060–400
:
The fans are mounted on rails. Remove one end of the fan assembly’s earth
braid. Loosen the screws (position 1) and the pins/screws (position 2) and pull
out the fan units (fan and motor are mounted on rails).
Size
480-1540
:
The fans are permanently mounted to rails. Access normally occurs through the
inspection door/doors. Fans mounted on rails can be pulled out if necessary.
Remove one end of the fan assembly’s earth braid. Loosen the screws (position
1) and the pins/screws (position 2) and pull out the fan units. NB! For multiple
fans, the screws securing all plates must be loosened.
2. Check that the fan impeller rotates easily, rotates in the right direction, is
in balance and does not vibrate. Also check that the fan impeller is clean
from any accumulation of particles. Imbalance may be due to a coating or
damage to the fan impeller blades.
3. Listen to the sound from the motor bearings. If the bearings are in good
condition, you will hear a slight purring sound. A scraping or pounding sound
may mean that the bearings are damaged and service is then required.
4. Check that the fan impellers are firmly mounted and that they overlap the
inlet cones.
Example, fan unit
1. Screw
2. Pin/screw