TABLE OF ALARMS IN THE DISPLAY
Alarm
Probable cause
Verification
Solution
Full Storage
Bin
Machine is
stopped
Thermostat failure
In the storage bin the ice
cubes do not touch the
thermostat rod
Check stock
thermostat
Cycle probe.
Machine is
stopped
Damaged cycle probe
Room temperature
information menu *****
Replace cycle probe
for a new one
Or replace for the
room temp. The
machine keeps
operating as if the
room temperature
was 20ºC
High
temperature
Machine is
stopped
Security pressure
switch
Check fan or compressor
Replace the
damaged pressure
switch
Lack of ventilation
Objects that block the
machine air inlet
Remove the objects
that block the air
flow
Dirty ventilation filter
clean with water
Dirty condenser
Clean the
condenser
Short time
Machine is
stopped
Ice cake formation in
the machine
Check condensation and
water inlet pressure
The showers do not
water
The pump does not work
Change the pump
The impulse tube is loose
Press the tube by its
joints
Long time
Machine is
stopped
The compressor or the
fan isn’t working
Output 1 information menu,
signal during manufacturing
process.
Change damaged
devices
The fan blades are in the
wrong position
Reposition the
blades
Hot gas valve
Won’t close
Replace valve
Low refrigeration
performance
Check refrigeration circuit
Water loss
Check electrovalve
Change damaged
devices
Lack of ventilation
Same as high temperature
Same as high
temperature