background image

6

d.

Based upon the mode of operation (“Flow” or “No-
Flow”) required, complete the appropriate steps to 
connect wires to flow switch. Use a Phillip’s head 
screwdriver to loosen and tighten switch terminal 
screws when attaching wires.

For “Flow” Mode of Operation (Fig. 1)

If the flow switch will be used to actuate a signal, 
alarm or other device when 

flow

occurs, connect 

the wire from that device to the “N.O.” contact.
Connect the “Hot” power supply wire to “C” terminal.

For “No Flow” Mode of Operation (Fig. 2)

If the flow switch will be used to actuate a signal, 
alarm or other device when 

no flow

occurs, connect 

the wire from that device to the “N.C.” contact.
Connect the “Hot” power supply wire to “C” terminal.

Flow

Opens

Circuit

Normally

closed

3

Common

1

Flow

Closes

Circuit

2

(

(

Normally

open

(

(

Common

(

(

FS4-3

LINE

LOAD

Fig. 1

HOT

3

1

2

FS4-3

LINE

LOAD

Fig. 2

HOT

3

1

2

c.

Determine which switch action is required for the 
flow switch.

• “Flow” means that the switch will close circuit 

C.-N.O. and open circuit C.-N.C. when flow rate 
is increased above setpoint of flow switch.

• “No Flow” means that the switch will open circuit 

C.-N.O. and close circuit C.-N.C. when flow rate 
is decreased below setpoint of flow switch.

NOTE:

Do not adjust these screws.

Содержание McDonnell & Miller FS1 Series

Страница 1: ...To prevent an electrical fire or equipment damage electrical wiring insulation must have a rating of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C To prevent electrocution when the electr...

Страница 2: ...tch operation rate of less than once per 2 5 minutes and any one cycle greater than 3 seconds on and 3 seconds off For applications with loads 0 5 and 38mA power fac tors exceeding 0 65 an anticipated...

Страница 3: ...n of the Flow Switch D 5 x D MINIMUM 1 2 PIPE 5 x D MINIMUM FLUID FLOW D PIPE DIAMETER The flow switch should be located in a horizontal section of pipe where there is a straight horizontal run of at...

Страница 4: ...hex fitting of flow switch and one wrench on connecting piping Tighten to following torque values 31 ft lb 42 N m for 1 2 pipe Repeat to connect pipe to opposite side of flow switch a Apply pipe seali...

Страница 5: ...trical Installation To prevent electrical shock turn off the electrical power before making electrical connections To prevent an electrical fire or equipment damage electrical wiring insulation must h...

Страница 6: ...itch will be used to actuate a signal alarm or other device when no flow occurs connect the wire from that device to the N C contact Connect the Hot power supply wire to C terminal Flow Opens Circuit...

Страница 7: ...quired flow switch may need to be adjusted OFF ON SECTION 4 Testing STEP 5 Adjustment 1 2 Pipe Connection Adjusting Screw Adjustment is necessary only if required flow no flow setpoints are above fact...

Страница 8: ......

Отзывы: