background image

GT_8-IOM Rev. 0    7/19

 

Printed in USA 

 
THIS INFORMATION IS SUBJECT TO THE CONTROLS OF THE EXPORT ADMINISTRATION REGULATIONS (EAR).  THIS INFORMATION SHALL NOT BE PROVIDED TO 
NON-US PERSONS OR TRANSFERRED BY ANY MEANS TO ANY LOCATION OUTSIDE THE UNITED STATES CONTRARY TO THE REQUIREMENTS OF THE EAR. 

 

 

 

 

 

ITT 

Conoflow 

105 Commerce Way 
Westminster, SC  29693 
Tel:  (864) 647-9521 
Fax: (864) 647-9568 

 

 

 
 

 

INSTRUCTION AND MAINTENANCE MANUAL 

GT_8 Series Milliamp I/P Transducer

 

 

CAUTION:  These instructions should be read and 
understood prior to installation, use or maintenance. 

 

GENERAL PRODUCT OVERVIEW 

 

This I/P transducer is a force-balanced unit which uses a fixed 
filtered air inlet pressure, accepts a DC milliamp input signal 
and converts it to a proportional air output pressure. 
Models are available with an integral relay booster (GT28, 
GT48, and GT68) or without the booster (GT18, GT38, and 
GT58).  All models are available in FM approvals 
explosionproof (XP) housings. 

 

 
SPECIFICATIONS 

 

Input Range: 

4-20 or 10-50 mA DC 

 

Nominal Impedance:

  4-20 mA model: 145 ohms 

 

10-50 mA model:  60 ohms 

 

Output Signal

3-15, 3-27 or 6-30 PSIG 
(21-103, 21-186 or 41-207 kPa) 

 

Required Air Supply:  GT18, GT28:

   25 PSIG (172 kPa) 

GT38, GT48, GT58 or GT68:

   

35 PSIG (241 kPa)  

 

Air Consumption:

 

GT18, GT28:

   0.20 scfm (6 slpm) max 

GT38, GT48, GT58 and GT68: 

0.30 scfm (8.5 slpm) max 

 

Air Delivery Rate:        GT18:  0.1

5 scfm (4.3 slpm) max

 

GT28:

  5 scfm (142 slpm) max 

GT38:  0.1

5 scfm (4.3 slpm) max

3

 

GT48:

  5 scfm (142 slpm) max

  

GT58:  0.1

5 scfm (4.3 slpm) max

3

 

 

GT68:

  5 scfm (142 slpm) max 

 

Exhaust Rate: 

GT18:  

0.17 scfm (5 slpm) max

3

 

 

GT28:

  1.7 scfm (50 slpm) max 

GT38:  

0.2 scfm (6 slpm) max

3

 

GT48:

  2.3 scfm (65 slpm) max

  

GT58:  

0.2 scfm (6 slpm) max

3

 

 

GT68:

  2.3 scfm (65 slpm) max 

 
 

Linearity: 

+/- 1.5% of output span 

 

Temperature Effect: 

0.2% of output span / 10 °F change 

 

For a 2 °F / minute rate of change

2

 

 

Temperature Range: 

0 °F to 150 °F (-18 °C to 66 °C) 

 

Approximate Weight: 

Approx.  7 lb (3.2 kg) – Std. Units 
Approx. 13 lb (5.9 kg) – XP Units 

 

Piping Requirements: 

3/8” Tubing or 1/4” Pipe (minimum) 

 
NOTES: 
 

1.  A Conoflow FR95 Airpak filter regulator or equivalent 

is recommended for the filtered air supply. 

2.  Models without a booster relay have a temperature 

effect rating of approximately 0.1% of output span / 10 
°F for a 2 °F / minute rate of change. 

3.  Low volume models (GT18, GT38, GT58) do not have 

a booster relay and should only be used in low 
volume flowrate applications. 

 
 

Prior to installation, inspect the package and 
product for damage.  Do not use if damaged.  Verify 
operation, and calibrate the transducer using the 
procedure on page 4. 
 
 

INSTALLATION 
 

See figure 1 (page 2) for location of connection interfaces 

 

ELECTRICAL CONNECTION:   The electrical connection for 
the input signal is made through a ½” NPSM or ½” NPT 
conduit connection on the side of the transducer housing body.  
Unscrew the cover and connect the positive lead to terminal 2 
and negative to terminal 1. 
 
For reverse acting models, connect the positive lead to 
terminal 1 and the negative lead to terminal 2. 
 
 

WARNING 

Conoflow’s products are designed and 
manufactured using materials and workmanship 
required to meet all applicable standards.  The use 
of these products should be confined to services 
specified and/or recommended in the Conoflow 
catalogs, instructions, or by Conoflow application 
engineers. 
 
To avoid personal injury or equipment damage 
resulting from misuse or misapplication of a 
product, it is necessary to select the proper 
materials of construction and pressure-
temperature ratings which are consistent with 
performance requirements.

 

Отзывы: