8
WARNING
Hazardous
voltage
Mount the controller in a well ventilated, shaded area using the supplied mounting screws. The controller must
be mounted vertically. Be sure to leave 8 inches of free air space on every side of the unit. The controller must
be in an area with an ambient between 0º F and 122º F.
Note
Do not block the heat sink (fi ns) and do not set anything on the controller.
Warning
The controller access cover should always be securely fastened to the control box due
to the dangerous voltage/shock hazard inside the unit. A padlock tab on the bottom of
the enclosure can be used to further restrict access
6. Power Supply and Wiring
Power Supply
Note
Installation and maintenance MUST be performed by properly trained and qualifi ed personnel.
Always follow the National Electric Code or Canadian Electric Code, as well as all local, state
and provincial codes when wiring the system.
The controller requires a single-phase power supply of 196 – 264 VAC on a dedicated two-pole circuit
breaker (not GFCI type). A dedicated circuit means no other appliances use the same circuit! The
output power from the controller is three-phase, variable frequency and variable voltage. Maximum
output voltage and frequency are line input voltage and 60 Hz, respectively. Motor must be 3 phase and
designed for the same voltage as supplied to the controller. For example, if the controller is supplied with
200 V, then the motor should be rated for 200 V.
Low supply voltage will reduce pump performance.
Refer
to table 1 for Circuit Breaker & Wire Sizing.
Table 1
Circuit Breaker & Wire Sizing
Wire Size AWG and Length (ft.)
Model
Controller
Circuit Breaker Generator Size
Input Output*
(If Used)
3AB2
#8, 178'
#14, 100'
30
8100 KVA
5AB2
#6,
184'
#12, 100'
50
13300 KVA
#10, 123'
75º C or higher rated UL listed copper wire.
Wire size and length in
bold
requires 90ºC rated wire.
* If there is more than 50 feet of wire from controller to motor, consult factory for selection of an output load fi lter (load reactor).
Wire and Conduit
Factory installed input and output power leads may be supplied with the controller. Use 75º C or higher rated
UL type copper wire. Use of Metal Conduit with Metal Conduit liquid tight Connectors is recommended for all
electrical connections.
5. Mounting the Controller
Hazardous
voltage
DANGER
Содержание Goulds Pumps AquaBoost II 3 HP
Страница 19: ...19 12 Controller Dimensions Figure 7...