Page 19
801P5 Smart Switch
TM
CHANGING THE SET POINTS
To change the set points, press the
[MENU]
key (See Figure 7).
The first menu item is SP1i, for Set point 1, increasing. To change
a set point:
1.
If you want to change a set point other than SP1i, select the
set point by pressing the arrow keys, then press
[SELECT]
.
The furthest right digit will blink.
2.
Use the
[SELECT]
key to move to the digit you want to
change.
3.
Use the
[UP/DOWN ARROW]
keys to change the value of
the digit.
4.
When the value is correct, press the
[SELECT]
key to move to
another digit. Repeat this until you have the correct value for
this set point.
5.
Use the
[STORE]
key to temporarily save the changes and
return to the main menu.
6.
Press
[RUN]
and then
[SELECT]
to permanently save the
setting and return to On-Line operation.
If you have set an invalid set point, the error message
EROR
will
be displayed. Possible causes for errors are:
•
INCREASE
value is equal to or lower than
DECREASE
value.
•
Values exceed range limits
•
Deadband is less than 1% of F.S.O.