Page 23
801P5 Smart Switch
TM
NOTE
NOTE
Pressure Calibration
(PCAL)
You can do a field pressure calibration using this function.
After
PCAL
is displayed, use the
[SELECT]
key to enter the
submenu.
LO-P
will be displayed for one second, and then
the switch’s interpretation of the actual pressure will be
displayed. Apply 0.0 psig to the unit. Use the
[UP/DOWN
ARROW]
keys to adjust the pressure display to zero psig.
Press the
[STORE]
key. The display will show
HI-P
for one
second, followed by the switch’s interpretation of the actual
pressure applied. Apply Full- Scale pressure to the unit. Use
the
[UP/DOWN ARROW]
keys to set the display equal to
Full- Scale pressure. Press the
[STORE]
key to return to the
main menu.
A pressure source is required for this operation. In addition,
calibration equipment used must have an accuracy of at least
± 0.02% F.S.O. of the switch being calibrated.
If re-calibration results in zero or Full-Scale readings that have
shifted by 4% F.S.O. or more from the factory calibration, an
error code of
EROR
will be displayed.
Reset (rSET)
This command resets the Smart-Switch
TM
to factory default
settings. After
rSET
appears, press
[SELECT], [STORE]
,
[RUN]
and
[SELECT]
to reset the unit to factory defaults.
These are as follows:
r-Hi
returns to factory F.S.O.
r-Lo
is set to zero
Spli
is set to 60% of the full range.
SPld
is set to 40% of the full range.
SP2i
is set to 70% of the full range.
SP2d
is set to 30% of the full range.
Switch delay is set to 0 mSec.
Display update time is set to 0.5 seconds.
All manuals and user guides at all-guides.com
Содержание Neo-Dyn 801P5
Страница 32: ...Page 28 Installation and Operation Manual All manuals and user guides at all guides com ...
Страница 38: ...Page 34 Installation and Operation Manual All manuals and user guides at all guides com ...
Страница 40: ...Page 36 Installation and Operation Manual All manuals and user guides at all guides com ...