3.11.3.

 

CDAR - Criterion recorder 

 

 Menu > Management  > Extensions > CDAR – Criterion recorder 

 
The criterion recorder application is used to record slowly changing signals in the protected object, e.g. motor 
start-up sequence. It saves analog values (RMS) and digital signals with sampling frequency 50 Hz. The user 
can  configure  the  number  of  registered  signals,  recording  time  before  triggering,  cause  of  the  start  of 
recording (binary inputs, binary outputs, digital signals from algorithms or programmable logic and increasing 
or decreasing values of analog signals). 
The window 

Criterion recorder

 allows the user to manage the work of a recorder. In particular it allows to 

trigger the criterion recorder from the user interface. 
For details, refer to the “Criterion Recorder User Manual”.

 

 

 

3.11.4.

 

PQA – Power Quality Analyzer 

 

 Menu > Management > Extensions > PQA – Power Quality Analyzer 

 
The  application  is  intended  for  energy  quality  analysis  in 
the  object  that  is  being  protected  according  to  PN  EN 
50160:2002,  PN  EN  61000-4-7  and  PN  EN  61000-4-30 
standards.  It  provides  the  THD  value  and  the  harmonic 
content  (up  to  the  40th)  of  phase  voltages  and  currents. 
The  THD  and  harmonic  content  values  are  used  in 
harmonic  protections,  that  enable  selective  localization  of 
faults,  e.g.  bearings  damage  in  motor  drives,  increase  in 
transformer core magnetization. 
The 

PQA  –  Power  Quality  Analyzer 

  window  displays  the 

averaged values, harmonic content and THD coefficient. 

 

 

 

3.11.5.

 

SLOG – System Log 

 

 Menu > Management > Extensions > SLOG - System Log 

 

System log stores information with date and time stamp, referring to logins of individual users, last change in 
set points, last cancelling of signalization, changes in profiles, bay view, parameters of communication ports, 
user commands. The log is accessible via SCADA system and ELF software tool. 

 

 

 

Содержание MUPASZ 710 plus

Страница 1: ...Bay control unit User manual Document version 05i00 Update 2015 01 22 energetyka itr org pl...

Страница 2: ...eserve the right to modify the device Tele and Radio Research Institute ICT and Electronics Centre 03 450 Warsaw ul Ratuszowa 11 tel faks 48 22 619 73 14 e mail energetyka itr org pl www energetyka or...

Страница 3: ...tection 26 3 11 2 DAR Fault recorder 26 3 11 3 CDAR Criterion recorder 27 3 11 4 PQA Power Quality Analyzer 27 3 11 5 SLOG System Log 27 3 11 6 UPS Uninterruptible Power Supply 28 3 11 7 RPS Redundant...

Страница 4: ...bay controller may have up to 8 bay types profiles implemented which may be freely modified and adapted to the user s requirements Logic function simulator is included The user may also redesign impl...

Страница 5: ...log outputs user commands Automatic functions AACF Automatic Active Component Forcing ACCB Automatic Connection of Capacitor Battery CBF Circuit Breaker Failure AUFLS Automatic Under Frequency Load Sh...

Страница 6: ...harm Tp bay working time I cumulated current resistance Rrotor Rhvt Measurements set two current 2 I1 2 I2 2 I3 voltage 2 U1 2 U2 2 U3 2 U12 2 U32 2 U13 frequency 2 f Diagnostic SC Selfcheck voltage...

Страница 7: ...lements of synoptic available switches electrical symbols lines nodes texts measurements clock states of binary inputs and outputs events messages signaling operational states Other functions 4 sets o...

Страница 8: ...ics grouped into sets of set points Texts Used to preview texts predefined in the device in supported languages and to edit editable texts Available via ELF program Selected counters Used to configure...

Страница 9: ...agnostic SC Self check monitoring of internal states of the device MAC Manual algorithm check simulates measurement values and allows verification of correct operation of an algorithm CBD Circuit brea...

Страница 10: ...or communication with ELF software tool Fig 2 1 1 Front panel 1 Freely programmable diodes diode descriptions on graphic display 2 Colour graphic 320x240 pixels display 3 Emergency opening signalizati...

Страница 11: ...e Local or Local and remote mode must be active Additionally access to the close command may be restricted for some users see Part 3 9 2 1 User Manager 2 1 2 Signal diodes In addition to graphic displ...

Страница 12: ...e contains the window caption i e the name of relevant branch or window the user is watching at 2 On the right hand side of the caption icons are located which inform about alarms locks and emergency...

Страница 13: ...ng id displayed in the bottom line For example in order to move from the main window to the Logging window the following path should be followed Menu Management Monitoring Logging or to use the Loggin...

Страница 14: ...isplaying it as not monitored Control activates the mechanism of switch control Activation of this option marks the main switch Another switch may be selected with the keys The switches which cannot b...

Страница 15: ...ing to the widow with descriptions of the other diodes 3 5 Event log Menu Event log Event log The Event log holds events generated in the device and allows their viewing Any recorded event is characte...

Страница 16: ...Lock Execution of an algorithm e g protection set to lock Lock or Temporary lock selected in Options Executed Execution of an algorithm e g protection 3 6 Measurements Menu Measurements Measurements...

Страница 17: ...rms Alarms MUPASZ 710 plus implements a series of switch bay protection algorithms In order to facilitate reading of operating state of algorithms the software of MUPASZ 710plus device is fitted with...

Страница 18: ...roup Selection of control If in the bay operation logic scheme the control mode selection is done via binary inputs then selection of the control mode via the user interface is disabled 3 8 2 User com...

Страница 19: ...he key the Control window opens In case the selected switch is not intended for control via the interface the message Lack of control is displayed If the selected operation is allowable it will be exe...

Страница 20: ...e set of settings being edited Menus of all sets of settings for a given profile are identical Algorithms of protections and automatic functions control and monitoring functions and nominal values are...

Страница 21: ...tarting edition of settings one should first set the nominal values Bay settings Nominals because their values may influence the way the protections and automatic functions operate and their operating...

Страница 22: ...out saving changes Edition of a NUMBER parameter consists in entering the number in accordance with the format and within allowable range The name of the edited parameter is displayed in the window he...

Страница 23: ...ogging in was lately used Producer and Service users have privileges allowing servicing of the devices these privileges are not granted to the operating personnel Activation of the Auto login function...

Страница 24: ...al Inputs outputs In this window current states of device binary inputs and outputs are displayed High state of input output is marked with the symbol low state with the _ symbol 3 9 3 Configuration 3...

Страница 25: ...ition of parameters 3 9 3 3 Date and time Menu Management Configuration Clock Menu Management Configuration Clock options After entering the Clock window in the first line current date and time is dis...

Страница 26: ...ow voltage CB trip coils what ensures CB opening even when no auxiliary supply is available in the switchgear Breaking current is also monitored and in case the maximum allowable local switch breaking...

Страница 27: ...al 3 11 4 PQA Power Quality Analyzer Menu Management Extensions PQA Power Quality Analyzer The application is intended for energy quality analysis in the object that is being protected according to PN...

Страница 28: ...the situation The system reaches full capacity after 10 minutes of charging 3 11 7 RPS Redundant Power Supply RPS solution consists of two independent power supplies The default power supply for the...

Страница 29: ...ring normal exploitation without disconnecting it from the network Basing on the acquired information the comprehensive breaker diagnostics is carried out including its wear and possible future malfun...

Страница 30: ...rator using an external test resistor HVT can work in manual and automatic modes In the manual mode the test is triggered by operator request In the automatic mode it is possible to test the generator...

Страница 31: ...unctions transfer inter bay lock messages synchronize internal clocks with system clock transmit content of recorders reprogramming of the device Each version of the device is accompanied by documenta...

Страница 32: ...hod for communication ports of devices installed at various locations of communication network are the same as for 2 wire version Type I 4 wire Fig 4 1 3 Intermediate position of the device in 4 wire...

Страница 33: ...tion of the device in 2 wire communication network Type II 2 wire Fig 4 2 2 Extreme position of the device in 2 wire communication network It is recommended that shielded twisted pair is used with cha...

Страница 34: ...ing particular attention to proper matching Tx and Rx transmission directions During transportation and when cables are not connected optical sockets should be protected with sealing caps If the optic...

Страница 35: ...hing It is recommended that the internal battery is replaced at least once every 10 years The battery should be replaced by service personnel as indicated by manufacturer Differences observed during c...

Страница 36: ...ded by a period of residence of the product in the repair Unauthorized tampering with the product will void the warranty Warranty does not cover damage resulting from improper use of the product 5 6 S...

Отзывы: