BIDIRECTIONAL LEVEL ITW
USER MANUAL
19
6.4. GENERAL SPECIFICATIONS FOR DIGITAL/ANALOG LEVEL ITW 8/8D-4A
MASTER / SLAVE:
Power
230Vac or 12Vdc stabilized
Max. consumption in Stand by 9.2W - 230Vca / 312mA – 12Vdc
Max. consumption in emission 13.8W a 230Vca / 1.512A – 12Vdc
Configuration
8 digital inputs (potential-free)
8 digital outputs through relay of 16Amp.
1 Relay of incidence
MASTER
4 analogical inputs (resolution 12 bits)
configurable by jumpers 0-20mA / 4-20mA / 0-5V / 0-10V
SLAVE
4 analogical outputs (resolution 12 bits)
configurable (in factory) 0-20mA / 4-20mA / 0-5V / 0-10V
LCD
Display inputs, outputs and incidences.
Presentation
polyamide box with 30% fiberglass, size 250*195*100 mm