background image

 

 

RLC-201

                            

 

DOC-RLC201-MNL Rev10.doc   (12/18/2020)

 

 Copyright 1999-2020 ITL, LLC

 

Page 13 

of 

15

Marker Alarm Setting 

 
The Marker Alarm Setting switch sets the number of marker lamps at which a marker 
alarm will be generated.  The switch is adjustable from zero to four lamps.  The factory 
default setting is one, meaning that a marker alarm will be generated when one or less 
marker lamps are burning. 

Manual Mode Select Switch 

 
The Manual Mode Select Switch overrides the photoelectric cell (PEC) to allow selection 
of Day mode or Night Mode for test or troubleshooting purposes.  The Day or Night Mode 
lights flash when in manual mode.  This switch should be left in the AUTO position for 
normal operation.  In the AUTO position the operating mode is determined by the 
photoelectric cell. 

Indicator Lights 

 

Indicator Lights 

Description 

Function 

DAY MODE 

Steady – Day mode operation via photoelectric cell. 
Flashing – Day mode operation via manual mode select switch. 

NITE MODE 

Steady – Night mode operation via photoelectric cell. 
Flashing – Night mode operation via manual mode select switch. 

CMD 

On when the RLC-201 commands the beacon to flash. 

CONF 

On when the RLC-201 confirms that the beacon is drawing the 
correct current. 

BCN ALM 

Steady – Indicates a beacon lamp alarm. 
Flashing – Indicates a flasher fail alarm (K3) 

MKR ALM 

Indicates a marker alarm. 

PEC ALM 

Indicates a photoelectric cell alarm  
(controller defaults to night mode on PEC alarm) 

BU ALM 

Indicates that the RLC-201 is operating the backup beacon. 

FIX 

Steady – Indicates the RLC-0201-GUI is receiving flash  
               synchronization data from GPS. 
Flashing – Indicates the RLC-0201-GUI is waiting for flash  
                 synchronization data from the GPS. 

PPS 

Provides visual indication of the pulse per second signal from the 
GPS. 

Содержание RLC-0201-GUI

Страница 1: ...Toll Free 1 866 624 8309 www itl llc com Installation and Operation Manual RLC 0201 UNI GUI Universal LED Incandescent A 1Controller...

Страница 2: ...ty period please contact ITL LLC in order to obtain a Return Authorization Number RMA In no event shall ITL LLC s liability exceed the price paid for the product from direct indirect special incidenta...

Страница 3: ...e serious injury and or death Do not attempt to service this equipment with line power applied Do not rely on interlock switches to remove lethal voltages from the system Measure for voltages using a...

Страница 4: ...ment 6 Obstruction Lights 6 Mechanical 6 Electrical 6 Installation 7 Unpacking your RLC 201 Controller 7 Quick Installation Guide 7 RLC 201 Controller Mounting 8 Electrical Connections 9 Connector Des...

Страница 5: ...stall test and troubleshoot the RLC 201 Product Description Both the RLC 0201 UNI and RLC 0201 GUI are capable of controlling one FAA type L 864 L red LED or FAA type L 864 incandescent beacon and up...

Страница 6: ...1700 or One Dialight D564 Series LED Beacon or One Dialight D464 Series LED Beacon or One Dialight D264 Series LED Beacon Side Lights Up to Five Incandescent 116W or 100W 120 or 230 Vac Up to Five LE...

Страница 7: ...nstall the RLC 201 controller Remove RLC 201 controller from packaging material Mount the RLC 201 enclosure Install FAA type L 864 Incandescent Beacon or FAA type L 864 L LED Beacon per manufacturer s...

Страница 8: ...RLC 201 DOC RLC201 MNL Rev10 doc 12 18 2020 Copyright 1999 2020 ITL LLC Page 8 of 15 RLC 201 Controller Mounting...

Страница 9: ...P2 P3 and P4 located at the bottom of the controller Connections for alarm relays are made on P5 and P6 located on the right side of the controller Typical connections for a 120VAC system are shown be...

Страница 10: ...or Terminals Function P1 L1 N Input Power Line Voltage Input Power Neutral P2 PRI N SEC Primary Beacon Power Supply Neutral Secondary Beacon P3 MKR N Marker Light Power L 810 obstruction light power M...

Страница 11: ...p and operation of the RLC 201 is performed using the Configuration Jumpers Configuration DIP Switches the Marker Alarm Setting dial and the Manual Mode Select Switch Configuration Jumpers Manual Mode...

Страница 12: ...N Marker alarm is disabled OFF Marker alarms is enabled 4 Beacon Type 1 ON ITL IFH 1900 or Dialight D464 or D564 5 Beacon Type 2 ON ITL IFH 1700 or Dialight D264 6 Marker Type See Marker Configuration...

Страница 13: ...ell Indicator Lights Indicator Lights Description Function DAY MODE Steady Day mode operation via photoelectric cell Flashing Day mode operation via manual mode select switch NITE MODE Steady Night mo...

Страница 14: ...Beacon LED MKR S750 0DH L 810 Obstruction Light Incandescent MKR LTG1 0IR L 810 L Obstruction Light LED with Infrared MKR LTE1 000 L 810 L Obstruction Light LED MKR LTE1 0IR L 810 L Obstruction Light...

Страница 15: ...ate Preparer Approval 10 Updated board layout pg 9 pg11 Updated Jumper configuration added IFH 1900 LTG Updated Spare Parts Replacement Parts List 12 18 2020 Prepared By Elke Hinson Approved By Josh C...

Отзывы: